UL 943
UL 943
Ground-Fault Circuit-
Interrupters
Underwriters Laboratories Inc. (UL)
333 Pfingsten Road
Northbrook, IL 60062-2096
UL Standard for Safety for Ground-Fault Circuit-Interrupters, UL 943
Third Edition, Dated August 27, 1993
Revisions: This Standard contains revisions through and including April 15, 2002. UL Standards for Safety
are developed and maintained in the Standard Generalized Markup Language (SGML). SGML -- an
international standard (ISO 8879-1986) -- is a descriptive markup language that describes a document’s
structure and purpose, rather than its physical appearance on a page. Due to formatting differences
resulting from the use of UL’s new electronic publishing system, please note that additional pages (on
which no requirements have been changed) may be included in revision pages due to relocation of
existing text and reformatting of the Standard.
Text that has been changed in any manner is marked with a vertical line in the margin. Changes in
requirements are marked with a vertical line in the margin and are followed by an effective date note
indicating the date of publication or the date on which the changed requirement becomes effective.
The revisions dated April 15, 2002 include a reprinted title page (page1) for this Standard.
As indicated on the title page (page 1), this UL Standard for Safety is an American National Standard.
Attention is directed to the note on the title page of this Standard outlining the procedures to be followed
to retain the approved text of this ANSI/UL Standard.
As indicated on the title page (page1), this UL Standard for Safety has been adopted by the Department
of Defense.
The master for this Standard at UL’s Northbrook Office is the official document insofar as it relates to a
UL service and the compliance of a product with respect to the requirements for that product and service,
or if there are questions regarding the accuracy of this Standard.
UL’s Standards for Safety are copyrighted by UL. Neither a printed copy of a Standard, nor the distribution
diskette for a Standard-on-Diskette and the file for the Standard on the distribution diskette should be
altered in any way. All of UL’s Standards and all copyrights, ownerships, and rights regarding those
Standards shall remain the sole and exclusive property of UL.
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or
transmitted in any form by any means, electronic, mechanical photocopying, recording, or otherwise
without prior permission of UL.
Revisions of UL Standards for Safety are issued from time to time. A UL Standard for Safety is current
only if it incorporates the most recently adopted revisions.
UL provides this Standard ″as is″ without warranty of any kind, either expressed or implied, including but
not limited to, the implied warranties of merchantability or fitness for any purpose.
In no event will UL be liable for any special, incidental, consequential, indirect or similar damages,
including loss of profits, lost savings, loss of data, or any other damages arising out of the use of or the
inability to use this Standard, even if UL or an authorized UL representative has been advised of the
possibility of such damage. In no event shall UL’s liability for any damage ever exceed the price paid for
this Standard, regardless of the form of the claim.
APRIL 15, 2002 − UL 943 tr1
UL will attempt to answer support requests concerning electronic versions of its Standards. However, this
support service is offered on a reasonable efforts basis only, and UL may not be able to resolve every
support request. UL supports the electronic versions of its Standards only if they are used under the
conditions and operating systems for which it is intended. UL’s support policies may change from
time-to-time without notification.
UL reserves the right to change the format, presentation, file types and formats, delivery methods and
formats, and the like of both its printed and electronic Standards without prior notice.
Purchasers of the electronic versions of UL’s Standards for Safety agree to defend, indemnify, and hold
UL harmless from and against any loss, expense, liability, damage, claim, or judgement (including
reasonable attorney’s fees) resulting from any error or deviation introduced while purchaser is storing an
electronic Standard on the purchaser’s computer system.
If a single-user version electronic Standard was purchased, one copy of this Standard may be stored on
the hard disk of a single personal computer, or on a single LAN file-server or the permanent storage
device of a multiple-user computer in such a manner that this Standard may only be accessed by one user
at a time and for which there is no possibility of multiple concurrent access.
If a multiple-user version electronic Standard was purchased, one copy of the Standard may be stored on
a single LAN file-server, or on the permanent storage device of a multiple-user computer, or on an Intranet
server. The number of concurrent users shall not exceed the number of users authorized.
Electronic Standards are intended for on-line use, such as for viewing the requirements of a Standard,
conducting a word search, and the like. Only one copy of the Standard may be printed from each
single-user version of an electronic Standard. Only one copy of the Standard may be printed for each
authorized user of a multiple-user version of an electronic Standard. Because of differences in the
computer/software/printer setup used by UL and those of electronic Standards purchasers, the printed
copy obtained by a purchaser may not look exactly like the on-line screen view or the printed Standard.
An employee of an organization purchasing a UL Standard can make a copy of the page or pages being
viewed for their own fair and/or practical internal use.
The requirements in this Standard are now in effect, except for those paragraphs, sections, tables, figures,
and/or other elements of the Standard having future effective dates as indicated in the note following the
affected item. The prior text for requirements that have been revised and that have a future effective date
are located after the Standard, and are preceded by a ″SUPERSEDED REQUIREMENTS″ notice.
New product submittals made prior to a specified future effective date will be judged under all of the
requirements in this Standard including those requirements with a specified future effective date, unless
the applicant specifically requests that the product be judged under the current requirements. However, if
the applicant elects this option, it should be noted that compliance with all the requirements in this
Standard will be required as a condition of continued and Follow-Up Services after the effective date, and
understanding of this should be signified in writing.
Copyright © 2002 Underwriters Laboratories Inc.
APRIL 15, 2002 − UL 943 tr2
This Standard consists of pages dated as shown in the following checklist:
Page Date
1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . April 15, 2002
2-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . September 18, 2000
4-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . April 15, 2002
6-8A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . September 18, 2000
8B . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . May 13, 1998
9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . August 27, 1993
10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . December 16, 1994
11-14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . August 27, 1993
15-16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . March 24, 1997
16A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . September 18, 2000
16B . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . May 13, 1998
17 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . January 4, 1995
18 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . September 18, 2000
19 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . August 27, 1993
20 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . May 13, 1998
21-24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . September 18, 2000
25-26B . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . May 13, 1998
27 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . September 18, 2000
28 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . August 27, 1993
29 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . September 18, 2000
30 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . May 13, 1998
30A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . September 18, 2000
30B . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . May 13, 1998
31. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . September 3, 1996
32 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . January 4, 1995
33-34 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . August 27, 1993
35 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . April 2, 1996
36 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . August 27, 1993
37 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . April 15, 2002
38-52A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . September 18, 2000
52B. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . April 15, 2002
53-58. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . September 18, 2000
SA1-SA2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . September 18, 2000
A1-A2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . May 13, 1998
APRIL 15, 2002 − UL 943 tr3
APRIL 15, 2002 − UL 943 tr4
No Text on This Page
AUGUST 27, 1993
(Title Page Reprinted: April 15, 2002)
1
UL 943
Standard for Ground-Fault Circuit-Interrupters
First Edition – December, 1972
Second Edition – September, 1985
Third Edition
August 27, 1993
This edition of UL 943, including all revisions, is approved as an American
National Standard. Approval of UL 943 as an American National Standard is
maintained using the continuous maintenance process. Comments or proposals
for revisions on any part of the Standard may be submitted to UL at any time.
Written comments are to be sent to UL-Melville Standards Department, 1285 Walt
Whitman Road, Melville, L.I., NY 11747.
An effective date included as a note immediately following certain requirements
is one established by Underwriters Laboratories Inc.
Approved as ANSI/UL 943-2002, March 12, 2002
The Department of Defense (DoD) has adopted UL 943 on November 30, 1984.
The publication of revised pages or a new edition of this Standard will not
invalidate the DoD adoption.
Revisions of this Standard will be made by issuing revised or additional pages
bearing their date of issue. A UL Standard is current only if it incorporates the
most recently adopted revisions, all of which are itemized on the transmittal notice
that accompanies the latest set of revised requirements.
ISBN 1-55989-465-2
COPYRIGHT © 1977, 2002 UNDERWRITERS LABORATORIES INC.
ANSI/UL 943-2002
SEPTEMBER 18, 2000 GROUND-FAULT CIRCUIT-INTERRUPTERS - UL 943 2
No Text on This Page
CONTENTS
FOREWORD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
INTRODUCTION
1 Scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
2 Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
3 Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6A
4 Units of Measurement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6A
5 References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6A
CONSTRUCTION
6 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6B
7 Resistance to Corrosion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6B
8 Rainproof Enclosures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6B
9 Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
10 Frame and Enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
10.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
10.2 Polymeric enclosures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
11 Provision for Wiring Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
12 Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
13 Accessibility of Energized Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
14 Internal Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
15 Field Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
16 Power-Supply Cord . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
17 Receptacles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
18 Spacings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
18A Alternate Spacings - Clearances and Creepage Distances . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
19 Operating Mechanism . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
20 Supervisory Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
PERFORMANCE
21 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
22 Leakage Current Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22A
23 Voltage Surge Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
24 High-Resistance Ground Faults Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26A
24.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26A
24.2 High-resistance ground fault test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
25 Resistance to False Tripping Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
26 Resistance to Environmental Noise Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34
27 Regulation Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .40
28 Normal Temperature Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .40
29 Dielectric Voltage-Withstand Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41
30 Overload and Motor Starting Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42
31 Low-Resistance Ground Fault Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .43
32 Endurance Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .45
33 Abnormal Operation Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .46
34 Extra-Low-Resistance Ground Faults Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .48
35 Short Circuit Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49
SEPTEMBER 18, 2000 GROUND-FAULT CIRCUIT-INTERRUPTERS - UL 943 2A
36 Chromic Acid Dropping Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .50
37 Dust Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .51
37A Permanence of Marking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .52
MARKINGS
38 Details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .52
38.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .52
38.2 Permanently connected ground-fault circuit-interrupters . . . . . . . . . . . . . . . . . . . . . . . . . .52A
38.3 Portable ground-fault circuit-interrupters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .52B
39 Installation Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .53
39.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .53
39.2 Permanently connected ground-fault circuit-interrupters . . . . . . . . . . . . . . . . . . . . . . . . . . .56
SUPPLEMENT SA - OPTIONAL 10 KA SHORT CIRCUIT CURRENT TEST FOR OUTLET-BOX TYPE
GROUND-FAULT CIRCUIT-INTERRUPTERS.
INTRODUCTION
SA1 Scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .SA1
PERFORMANCE
SA2 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .SA1
MARKINGS
SA3 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .SA2
APPENDIX A
Standards for Components. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A1
SEPTEMBER 18, 2000 GROUND-FAULT CIRCUIT-INTERRUPTERS - UL 943 2B
SEPTEMBER 18, 2000 GROUND-FAULT CIRCUIT-INTERRUPTERS - UL 943 3
No Text on This Page
FOREWORD
A. This Standard contains basic requirements for products covered by Underwriters Laboratories Inc. (UL)
under its Follow-Up Service for this category within the limitations given below and in the Scope section
of this Standard. These requirements are based upon sound engineering principles, research, records of
tests and field experience, and an appreciation of the problems of manufacture, installation, and use
derived from consultation with and information obtained from manufacturers, users, inspection authorities,
and others having specialized experience. They are subject to revision as further experience and
investigation may show is necessary or desirable.
B. The observance of the requirements of this Standard by a manufacturer is one of the conditions of the
continued coverage of the manufacturer’s product.
C. A product which complies with the text of this Standard will not necessarily be judged to comply with
the Standard if, when examined and tested, it is found to have other features which impair the level of
safety contemplated by these requirements.
D. A product that contains features, characteristics, components, materials, or systems new or different
from those covered by the requirements in this standard, and that involves a risk of fire or of electric shock
or injury to persons shall be evaluated using appropriate additional component and end-product
requirements to maintain the level of safety as originally anticipated by the intent of this standard. A
product whose features, characteristics, components, materials, or systems conflict with specific
requirements or provisions of this standard does not comply with this standard. Revision of requirements
shall be proposed and adopted in conformance with the methods employed for development, revision, and
implementation of this standard.
E. UL, in performing its functions in accordance with its objectives, does not assume or undertake to
discharge any responsibility of the manufacturer or any other party. The opinions and findings of UL
represent its professional judgment given with due consideration to the necessary limitations of practical
operation and state of the art at the time the Standard is processed. UL shall not be responsible to anyone
for the use of or reliance upon this Standard by anyone. UL shall not incur any obligation or liability for
damages, including consequential damages, arising out of or in connection with the use, interpretation of,
or reliance upon this Standard.
F. Many tests required by the Standards of UL are inherently hazardous and adequate safeguards for
personnel and property shall be employed in conducting such tests.
APRIL 15, 2002 GROUND-FAULT CIRCUIT-INTERRUPTERS - UL 943 4
INTRODUCTION
1 Scope
1.1 These requirements cover ground-fault circuit-interrupters intended for use only in alternating-current
circuits wherein one of the wires is grounded in accordance with the National Electrical Code. These
devices are intended for use on 120 Vac or 120/240 Vac, 60 Hz circuits.
1.2 These requirements do not cover ground-fault circuit-interrupters intended for use in circuits served
by a transformer having windings wholly insulated from each other.
1.3 A ground-fault circuit-interrupter as covered by these requirements is a device whose function is to
interrupt the electric circuit to the load when a fault current to ground exceeds some predetermined value
that is less than that required to operate the overcurrent protective device of the supply circuit.
1.4 Deleted April 15, 2002
2 Glossary
2.1 ACCESSIBLE PART – A part so located that it can be contacted by a person, either directly or by
means of a probe or tool.
2.2 AUTOMATIC RECLOSURE – Denotes the act of a ground-fault circuit-interrupter resetting itself
after having been tripped.
2.3 CLASS A – Denotes a ground-fault circuit-interrupter that will trip when a fault current to ground is
6 mA or more.
2.4 CLASS B – Denotes a ground-fault circuit-interrupter that will trip when a fault current to ground is
20 mA or more.
2.5 CORD-CONNECTED – Denotes connection to a supply circuit by way of a flexible cord terminating
in an attachment plug.
2.6 DOUBLE INSULATION – The insulation system resulting from a combination of functional and
supplementary insulation.
2.7 ENERGIZED PART – A part at some potential with respect to another part, or to earth.
2.8 FUNCTIONAL INSULATION – The insulation necessary for the proper functioning of the device,
and for basic protection against electrical shock hazard.
2.9 GROUND FAULT – Denotes an unintentional electrical path between a part operating normally at
some potential to ground, and ground.
APRIL 15, 2002 GROUND-FAULT CIRCUIT-INTERRUPTERS - UL 943 5
2.10 LEAKAGE CURRENT – Denotes all currents including capacitively coupled currents which may be
conveyed between energized parts of a circuit and (1) ground or (2) other parts.
2.10.1 OUTLET-BOX TYPE GROUND-FAULT CIRCUIT-INTERRUPTER – A permanently connected
ground-fault circuit-interrupter provided with a mounting yoke for mounting in an outlet box; may or may
not be provided with receptacle outlets. May be referred to as a receptacle-type GFCI.
2.10.1 added March 24, 1997
2.11 PERMANENTLY CONNECTED – Denotes connection to a supply circuit by way of fixed electrical
conductors.
2.12 PORTABLE GROUND-FAULT CIRCUIT-INTERRUPTER – A plug-in type ground-fault circuit-
interrupter provided with male blades for connection to a receptacle, or one that is cord-connected. (See
2.5).
2.13 RAINPROOF – Denotes a ground-fault circuit-interrupter so constructed as to prevent rain from
interfering with its successful operation.
2.14 RATED CURRENT – The marked value of current.
2.15 RATED VOLTAGE – For devices with a marked voltage within the range of 110– 125 V, the rated
voltage is to be considered to be 120 V. For devices with an additional marked voltage within the range
of 190 – 250 V, the rated voltage is considered to be 120/240 V.
2.16 REINFORCED INSULATION – An insulation providing protection against electrical shock hazard
that is equivalent to double insulation.
2.17 ROOM TEMPERATURE – Air at 25.0 ±5.0°C (77.0±9.0°F).
2.18 SHOCK HAZARD – A shock hazard is considered to exist at a part of a ground-fault circuit-
interrupter if:
a) There would be current of 6 mA or more in a resistance of 500 ohms connected between
the part in question and the grounded supply conductor, and
b) The device would not operate to open the circuit to the 500-ohm resistor within the time
allowed in 24.1.1
2.19 SUPPLEMENTARY INSULATION – An independent insulation provided in addition to the
functional insulation to insure protection against electric shock hazard in the event that functional
insulation should fail.
2.20 TRIP – Denotes automatic interruption by the ground-fault circuit-interrupter of the electric circuit
to the load.
SEPTEMBER 18, 2000 GROUND-FAULT CIRCUIT-INTERRUPTERS - UL 943 6
3 Components
3.1 Except as indicated in 3.2, a component of a product covered by this standard shall comply with the
requirements for that component. See Appendix A for a list of standards covering components used in the
products covered by this standard.
3.1 revised September 18, 2000
3.2 A component is not required to comply with a specific requirement that:
a) Involves a feature or characteristic not required in the application of the component in the
product covered by this standard, or
b) Is superseded by a requirement in this standard.
3.2 revised September 18, 2000
3.3 A component shall be used in accordance with its rating established for the intended conditions of
use.
3.3 revised September 18, 2000
3.4 Specific components are incomplete in construction features or restricted in performance capabilities.
Such components are intended for use only under limited conditions, such as certain temperatures not
exceeding specified limits and shall be used only under those specific conditions.
3.4 revised September 18, 2000
4 Units of Measurement
4.1 Values stated without parentheses are the requirement. Values in parentheses are explanatory or
approximate information.
4.1 revised September 18, 2000
5 References
5.1 Any undated reference to a code or standard appearing in the requirements of this standard shall be
interpreted as referring to the latest edition of that code or standard.
SEPTEMBER 18, 2000 GROUND-FAULT CIRCUIT-INTERRUPTERS - UL 943 6A
CONSTRUCTION
6 General
6.1 The design, workmanship, and degree of production uniformity shall be such that the reliability of the
ground-fault circuit-interrupter to perform the functions evaluated by the requirements will be high.
6.2 A ground-fault circuit-interrupter intended to serve also as a junction box for swimming-pool
equipment shall comply with the applicable requirements covering swimming-pool junction boxes, UL
1241.
6.3 Male and female contact devices such as plugs, connectors, current taps, and receptacles provided
with, or as an integral part of, a ground-fault circuit-interrupter shall also comply with the applicable
construction and performance requirements from the Standard for Attachment Plugs and Receptacles, UL
498.
Added 6.3 effective July 4, 1998
7 Resistance to Corrosion
7.1 Parts shall be protected against corrosion if failure of such parts would be likely to result in a
hazardous condition, including failure to perform with high-resistance ground faults as provided in these
requirements.
8 Rainproof Enclosures
8.1 A rainproof enclosure shall be so constructed as to exclude a beating rain. The enclosure shall be
provided with external means for mounting, except that internal means for mounting may be employed if
so designed as to prevent water from entering the enclosure. Metals shall not be used in combination
such as to cause galvanic action which will affect adversely any part of the device.
8.2 A rainproof ground-fault circuit-interrupter is to be attached to a vertical clapboard surface as in actual
service. If there is provision for conduit connection at points above the lowest insulation or live part of the
ground-fault circuit-interrupter, an unspecified length of conduit is to be attached with the torque specified
in 11.4. The unattached end of the conduit is to be covered to prevent entry of water during this test. A
water spray is to be applied from three nozzles so located as to direct the spray against all surfaces that
would be exposed to a beating rain. The device is considered to comply with the provisions of 8.1 if there
is no entry of water above the lowest insulation or live part of the ground-fault circuit-interrupter.
8.3 An elastomeric material, employed to obtain compliance with the provisions of 8.1 shall be adequately
resistant to deterioration.
8.4 In order to determine compliance with the provisions of 8.3, a gasket of rubber or neoprene or a
composition thereof is to be exposed for 96 hours to oxygen at a gauge pressure of 300 ±10 psi (2.07
±0.07 MN/m 2 ) gauge and a temperature of 70.0 ±1.0°C (158.0±1.8°F). There is to be no visible evidence
of deterioration, or change in hardness of more than 5 numbers (0.0005 inch or 0.013 mm).
8.4 revised December 16, 1994
SEPTEMBER 18, 2000 GROUND-FAULT CIRCUIT-INTERRUPTERS - UL 943 6B
8.5 Except for threaded holes, there shall not be provision for conduit located above any live part or
insulation of the ground-fault circuit-interrupter.
8.6 There shall be provision for drainage of the enclosure, provided that holes for this purpose are to be
no larger than 1/4 by 1/4 inch (6.4 by 6.4 mm).
8.7 A rainproof enclosure made of sheet steel having a thickness of 0.120 inch (3.05 mm) or more shall
be protected against corrosion by one of the following coatings:
a) Hot dipped mill galvanized sheet steel conforming with the coating designation G60 or A60
in Table 1 of the Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-
Coated (Galvannealed) by the Hot-Dip Process, ASTM A653/A653M-94, with not less than 40
percent of the zinc on any side, based on the minimum single spot test requirement in this
ASTM Specification. The weight of zinc coating may be determined by any acceptable method;
however, in case of question the weight of coating shall be established in accordance with the
test method of ASTM A90-81(1991). An A60 (alloyed) coating shall also comply with 8.10.
b) A zinc coating, other than that provided on hot dipped mill galvanized sheet steel, uniformly
applied to an average thickness of not less than 0.00041 inch (0.010 mm) on each surface with
a minimum thickness of 0.00034 inch (0.009 mm). The thickness of the coating shall be
established by the Chromic Acid Dropping Test, Section 36. An annealed coating shall also
comply with 8.10.
c) Two coats of an organic finish of the epoxy or alkyd-resin type or other outdoor paint on both
surfaces. The suitability of the paint may be determined by consideration of its composition or
by corrosion tests if these are considered necessary.
8.7 revised April 2, 1996
8.8 A rainproof enclosure made of sheet steel having a thickness of less than 0.120 inch (3.05 mm) shall
be protected against corrosion by one of the following coatings:
a) Hot dipped mill galvanized sheet steel conforming with the coating Designation G90 in Table
1 of the Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated
(Galvannealed) by the Hot-Dip Process, ASTM A653/A653M-94, with not less than 40 percent
of the zinc on any side, based on the minimum single spot test requirement in this ASTM
Specification. The weight of zinc coating may be determined by any suitable method; however,
in case of question the weight of coating shall be established in accordance with the test
method of ASTM A90-81(1991).
b) A zinc coating, other than that provided on hot dipped mill galvanized sheet steel, uniformly
applied to an average thickness of not less than 0.00061 inch (0.015 mm) on each surface with
a minimum thickness of 0.00054 inch (0.014 mm). The thickness of the coating shall be
established by the Chromic Acid Dropping Test, Section 36. An annealed coating shall also
comply with 8.10.
c) A cadmium coating not less than 0.001 inch (0.025 mm) thick on both surfaces. The
thickness of coating shall be established by the Chromic Acid Dropping Test, Section 36.
d) A zinc coating conforming with item a) or b) of 8.7 with one coat of outdoor paint as
specified in item c of 8.7.
SEPTEMBER 18, 2000 GROUND-FAULT CIRCUIT-INTERRUPTERS - UL 943 7
e) A cadmium coating not less than 0.00075 inch (0.019 mm) thick on both surfaces with one
coat of outdoor paint on both surfaces, or not less than 0.00051 inch (0.013 mm) thick on both
surfaces with two coats of outdoor paint on both surfaces. The thickness of the cadmium
coating shall be established by the Chromic Acid Dropping Test, Section 36 and the paint shall
be as specified in item c of 8.7.
8.8 revised April 2, 1996
8.9 With reference to 8.7 and 8.8, other finishes, including paints, special metallic finishes and
combinations of the two may be accepted when comparative tests with galvanized sheet steel (without
annealing, wiping, or other surface treatment) conforming with item a of 8.7 or 8.8, as applicable, indicate
they provide equivalent protection. Among the factors which are taken into consideration when judging the
suitability of such coating systems are exposure to salt spray, moist carbon dioxide sulphur dioxide-air
mixtures, moist hydrogen sulphide-air mixtures, ultraviolet light and water.
8.10 A hot dipped mill-galvanized A60 (alloyed) coating or an annealed coating on sheet steel which is
bent or similarly formed or extruded or rolled at edge of holes after annealing shall additionally be painted
in the bent or formed area if the bending or forming process damages the zinc coating.
SEPTEMBER 18, 2000 GROUND-FAULT CIRCUIT-INTERRUPTERS - UL 943 8
SEPTEMBER 18, 2000 GROUND-FAULT CIRCUIT-INTERRUPTERS - UL 943 8A
No Text on This Page
MAY 13, 1998 GROUND-FAULT CIRCUIT-INTERRUPTERS - UL 943 8B
No Text on This Page
8.11 If flaking or cracking of the zinc coating at the outside radius of the bent or formed section is visible
at 25 power magnification, the zinc coating is considered damaged. Simple sheared or cut edges and
punched holes are not considered to be formed.
9 Grounding
9.1 All accessible parts of a permanently connected ground-fault circuit-interrupter that are likely to
become energized if there should be arc-over, insulation failure, or the like, shall be connected together
and to the terminals intended for the equipment grounding conductor (see 15.1). The resistance of the
circuit is not to exceed 0.1 ohm, and the circuit shall be capable of withstanding continuously a current of
25 A.
9.2 In considering the provisions of 9.1, a grounded or insulating barrier may be employed to reduce the
likelihood that accessible parts will become energized.
9.3 If provided, the equipment grounding conductor of a portable or cord-connected ground-fault
circuit-interrupter shall be conductively connected to the grounding contacts of the attachment plug and of
the receptacles, and shall not be connected to accessible conductive parts.
10 Frame and Enclosure
10.1 General
10.1.1 A ground-fault circuit-interrupter shall be so formed and assembled that it can withstand the
abuses to which it might be subjected without affecting spacings, insulation, accessibility of live parts,
performance with high-resistance ground faults, or grounding, to the extent that the device would fail to
comply with these requirements.
10.1.2 Opening or removal of a door or cover, with or without the use of a separate tool, that must be
opened or removed in order to properly use or install a ground-fault circuit-interrupter shall not increase
the likelihood of accidental injury to any part depended upon for the proper functioning of the device. The
likelihood of such injury will not be considered to have increased if the part in question has not become
accessible. See items a and b of 13.2.
10.1.3 Among the factors taken into consideration when the acceptability of enclosure material is being
determined, are (1) physical strength, (2) resistance to moisture absorption, (3) combustibility, (4)
resistance to corrosion, and (5) resistance to distortion at temperatures to which the enclosure may be
subjected under conditions of normal or abnormal use. For a nonmetallic enclosure, all of these factors
are considered with respect to thermal aging.
10.1.4 An enclosure of sheet metal having the construction indicated in Table 10.1 or 10.2 will generally
be considered to have an acceptable level of the factors shown in 10.1.3.
10.1.5 In determining compliance with the provisions of 10.1.1, a permanently connected ground-fault
circuit-interrupter is to be subjected to an externally applied impact of 5 ft-lbs (6.8 J) applied by way of a
solid, smooth, steel sphere 2 inches (50.8 mm) in diameter.
Exception: Receptacle-type ground-fault circuit-interrupters are to be subjected to a 3-ft (0.91 m) drop
test onto a concrete floor. The method of doing the test shall be in accordance with the provisions of
10.1.8.
AUGUST 27, 1993 GROUND-FAULT CIRCUIT-INTERRUPTERS - UL 943 9
10.1.6 The sphere mentioned in 10.1.5 is to be allowed to fall freely from rest through the distance
required to cause the specified impact upon the surface under test. For surfaces other than horizontal, the
sphere may be suspended by a cord and allowed to fall as a pendulum through the required distance. The
ground-fault circuit-interrupter is to be placed against a vertical wall with the surface to be tested in the
same vertical plane as the point of support of the pendulum.
Table 10.1
Thickness of sheet metal for enclosures – carbon steel or stainless steel a
Table 10.1 revised December 16, 1994
Without supporting frame b
With supporting frame or equivalent
reinforcing b
Minimum thickness inches (mm)
Maximum width c Maximum length d Maximum width c Maximum length d
Inches (cm) Inches (cm) Inches (cm) Inches (cm) Uncoated Metal coated
4.0 (10.2) Not limited 6.25 (15.9) Not limited 0.020 e,f (0.51) 0.023 e,f (0.58)
4.75 (12.1) 5.75 (14.6) 6.75 (17.1) 8.25 (21.0)
6.0 (15.2) Not limited 9.5 (24.1) Not limited 0.026 e,f (0.66) 0.029 e,f (0.74)
7.0 (17.8) 8.75 (22.2) 10.0 (25.4) 12.5 (31.8)
8.0 (20.3) Not limited 12.0 (30.5) Not limited 0.032 (0.81) 0.034 (0.86)
9.0 (22.9) 11.5 (29.2) 13.0 (33.0) 16.0 (40.6)
12.5 (31.8) Not limited 19.5 (49.5) Not limited 0.042 (1.07) 0.045 (1.14)
14.0 (35.6) 18.0 (45.7) 21.0 (53.3) 25.0 (63.5)
18.0 (45.7) Not limited 27.0 (68.6) Not limited 0.053 (1.35) 0.056 (1.42)
20.0 (50.8) 25.0 (63.5) 29.0 (73.7) 36.0 (91.4)
22.0 (55.9) Not limited 33.0 (83.8) Not limited 0.060 (1.52) 0.063 (1.60)
25.0 (63.5) 31.0 (78.7) 35.0 (88.9) 43.0 (109.2)
25.0 (63.5) Not limited 39.0 (99.1) Not limited 0.067 (1.70) 0.070 (1.78)
29.0 (73.7) 36.0 (91.4) 41.0 (104.1) 51.0 (129.5)
33.0 (83.8) Not limited 51.0 (129.5) Not limited 0.080 (2.03) 0.084 (2.13)
38.0 (96.5) 47.0 (119.4) 54.0 (137.2) 66.0 (167.6)
42.0 (106.7) Not limited 64.0 (162.6) Not limited 0.093 (2.36) 0.097 (2.46)
47.0 (119.4) 59.0 (149.9) 68.0 (172.7) 84.0 (213.4)
52.0 (132.1) Not limited 80.0 (203.2) Not limited 0.108 (2.74) 0.111 (2.82)
60.0 (152.4) 74.0 (188.0) 84.0 (213.4) 103.0 (261.6)
63.0 (160.0) Not limited 97.0 (246.4) Not limited 0.123 (3.12) 0.126 (3.20)
73.0 (185.4) 90.0 (228.6) 103.0 (261.6) 127.0 (322.6)
a
Tables 10.1 and 10.2 are based upon the initial deflection of an enclosure surface with a concentrated load at the center of
the surface.
b
A supporting frame is a structure of angle or channel or a folded rigid section of sheet metal that is rigidly attached to and
has essentially the same outside dimensions as the enclosure surface and which has sufficient torsional rigidity to resist the
bending moments which may be applied via the enclosure surface when it is deflected. Construction that is considered to have
equivalent reinforcing may be accomplished by designs that will produce a structure that is as rigid as one built with a frame of
angles or channels. Construction considered to be without supporting frame includes: (1) single sheet with single-formed
flanges (formed edges), (2) a single sheet which is corrugated or ribbed, and (3) an enclosure surface loosely attached to a
frame, for example, with spring clips.
c
The width is the smaller dimension of a rectangular sheet metal piece which is part of an enclosure. Adjacent surfaces of an
enclosure may have supports in common and be made of a single sheet.
d
For panels which are supported along one side (for example, side panels of boxes) the length of the unsupported side shall
be limited to the dimensions specified.
e
Sheet steel for a rainproof enclosure is to be not less than 0.034 inch thick if zinc-coated and not less than 0.032 inch thick if
uncoated.
f
Sheet steel is to be not less than 0.032 inch thick if uncoated and not less than 0.034 inch thick if zinc-coated at points to
which a wiring system is to be attached.
DECEMBER 16, 1994 GROUND-FAULT CIRCUIT-INTERRUPTERS - UL 943 10
Table 10.2
Thickness of sheet metal for enclosures – aluminum, copper, or brass a
Without supporting frame b
With supporting frame or equivalent
reinforcing b
Maximum width c Maximum length d Maximum width c Maximum length d Minimum acceptable
thickness
Inches (cm) Inches (cm) Inches (cm) Inches (cm) Inches (mm)
3.0 (7.6) Not limited 7.0 (17.8) Not limited 0.023 e,f (0.58)
3.5 (8.9) 4.0 (10.2) 8.5 (21.6) 9.5 (24.1)
4.0 (10.2) Not limited 10.0 (25.4) Not limited 0.029 f (0.74)
5.0 (12.7) 6.0 (15.2) 10.5 (26.7) 13.5 (34.3)
6.0 (15.2) Not limited 14.0 (35.6) Not limited 0.036 f (0.91)
6.5 (16.5) 8.0 (20.3) 15.0 (38.1) 18.0 (45.7)
8.0 (20.3) Not limited 19.0 (48.3) Not limited 0.045 (1.14)
9.5 (24.1) 11.5 (29.2) 21.0 (53.3) 25.0 (63.5)
12.0 (30.5) Not limited 28.0 (71.1) Not limited 0.058 (1.47)
14.0 (35.6) 16.0 (40.6) 30.0 (76.2) 37.0 (94.0)
18.0 (45.7) Not limited 42.0 (106.7) Not limited 0.075 (1.91)
20.0 (50.8) 25.0 (63.4) 45.0 (114.3) 55.0 (139.7)
25.0 (63.5) Not limited 60.0 (152.4) Not limited 0.095 (2.41)
29.0 (73.7) 36.0 (91.4) 64.0 (162.6) 78.0 (198.1)
37.0 (94.0) Not limited 87.0 (221.0) Not limited 0.122 (3.10)
42.0 (106.7) 53.0 (134.6) 93.0 (236.2) 114.0 (289.6)
52.0 (132.1) Not limited 123.0 (312.4) Not limited 0.153 (3.89)
60.0 (152.4) 74.0 (188.0) 130.0 (330.2) 160.0 (406.4)
a–d
See notes a–d to Table 10.1.
e
Sheet copper, brass, or aluminum for a raintight enclosure is to be not less than 0.029 inch in thickness.
f
Nonferrous metal is to be not less than 0.045 inch thick at points to which a wiring system is to be attached.
10.1.7 The surfaces mentioned in 10.1.6 are those exposed during normal service, including operating
handles, pushbuttons, and the like. Doors that are hinged or sliding or otherwise captive, and covers that
cannot be removed without tools, are to be closed. Other doors or covers are to be opened or removed.
A sample that has been struck is not required to withstand another blow. However, if more than one blow
is applied to a single sample, a failure after the first blow is to be disregarded provided that the same
surface withstands a blow on another sample. If a device fails during the first test, the device is considered
to have failed.
10.1.8 A cord-connected or portable device is to be allowed to fall from a height of three feet such that a
different part will strike a hardwood surface in each of three drops. Doors or covers are to be moved to
any position likely in normal service providing that a captive door or cover is not forced to remain in any
position by some means not part of the ground-fault circuit-interrupter.
10.1.9 The hardwood surface mentioned in 10.1.8 is to consist of a layer of nominal 1-inch
tongue-and-groove oak flooring mounted on two layers of 3/4-inch (19 mm) plywood. The surface is to be
a square 4 ft (1.2 m) on a side. The assembly is to rest on a concrete floor or the equivalent.
AUGUST 27, 1993 GROUND-FAULT CIRCUIT-INTERRUPTERS - UL 943 11
10.1.10 The maximum acceptable moment, center of gravity, dimensions, and weight of a direct plug-in
unit shall comply with the requirements specified in Items a, b, c and d. See Figure 10.1 and 10.1.11 and
10.1.12.
a) The quotient of WY/Z shall not exceed 48 ounces (1361 g).
b) The quotient of WY/S shall not exceed 48 ounces (1361 g).
c) The product of WX shall not exceed 80 ounce-inches (0.56 N·m).
d) The weight of a unit shall not exceed 28 ounces (794 g).
10.1.11 Definitions for the symbols used in 10.1.10 are as follows:
W is the weight of the unit in ounces (g).
Y is the distance illustrated in Figure 10.1 in inches (mm).
Z is the lesser of the two distances, Z1 or Z2, as illustrated in Figure 10.1, in inches (mm).
S is the lesser of the two distances, S1 or S2, as illustrated in Figure 10.1, in inches (mm).
X is the greater of the two distances X1 or X2, as illustrated in Figure 10.1, in inches (mm).
This is generated text for figtxt.
Figure 10.1
Dimensions of a direct plug-in unit
AUGUST 27, 1993 GROUND-FAULT CIRCUIT-INTERRUPTERS - UL 943 12
10.1.12 The moment and weight specified in 10.1.10 are to be determined as follows:
a) For units with an output cord, the cord is to be cut off at the enclosure, or at the strain relief
means if the strain relief means is outside the enclosure.
b) For units with integrally mounted accessories or optional components, the values are to be
measured with the accessories or components in place.
10.1.13 When inserted in a parallel-bladed duplex receptacle, any part of a unit, including output wiring,
shall not interfere with full insertion of an attachment plug into the adjacent receptacle. See Figure 10.2.
Exception: A unit that renders the adjacent receptacle completely unusable in any one mounting position
is acceptable.
This is generated text for figtxt.
Figure 10.2
Parallel duplex receptacle
AUGUST 27, 1993 GROUND-FAULT CIRCUIT-INTERRUPTERS - UL 943 13
10.2 Polymeric enclosures
10.2.1 A polymeric enclosure, or a polymeric part of an enclosure, shall comply with the applicable
requirements for enclosures as specified in the Standard for Polymeric Materials – Use in Electrical
Equipment Evaluations, UL 746C.
Exception: For a direct plug-in ground-fault circuit-interrupter, the crushing test shall be conducted in
accordance with 71 of the Standard for Attachment Plugs and Receptacles, UL 498.
10.2.2 An adhesive used in the assembly of a ground-fault circuit-interrupter shall comply with the
applicable requirements for adhesives as specified in the Standard for Polymeric Materials – Use in
Electrical Equipment Evaluations, UL 746C.
Exception: Methods utilizing fusion techniques, such as solvent cementing, ultrasonic welding,
electromagnetic induction, and thermal welding need not be investigated.
11 Provision for Wiring Systems
11.1 There shall be provision at a permanently connected ground-fault circuit-interrupter for attachment
of raceway or cable in accordance with the National Electrical Code, ANSI/NFPA 70.
11.2 A knockout in a sheet-metal enclosure shall be secure but shall be capable of being removed
without significant deformation of the enclosure, or dislocating larger sizes of a multiple knockout. A
knockout likely to be used during installation shall be surrounded by a flat surface for effective seating of
a conduit bushing and shall be so located that installation of a bushing will not result in spacings smaller
than those allowed in these requirements.
11.3 A hole tapped for the attachment of threaded rigid conduit shall be so constructed as to permit:
a) The attachment of a conduit bushing, or there is to be a smooth, well-rounded passage for
wires equivalent to that presented by a bushing, and
b) For raintight equipment, the application of tightening torque as specified in 11.4.
11.4 The torque mentioned in 8.2 and 11.3 is to be applied to the conduit in such a manner as to prevent
the application of a bending movement to the assembly. The value of torque is to be 800 lbf-in (90 N·m)
for 3/4-inch (19-mm) and smaller trade sizes of conduit, 1000 lbf-in (113 N·m) for sizes larger than 3/4 inch
(19 mm) up to 1-1/2 inches (38 mm), and 1600 lbf-in (181 N·m) for sizes larger than 1-1/2 inches (38 mm).
12 Connections
12.1 Except as described in 12.2 and 12.3, a portable cord-connected ground-fault circuit-interrupter
provided with an equipment grounding conductor shall have double insulation or reinforced insulation
throughout its construction, or if not provided with an equipment grounding conductor shall have double
insulation or reinforced insulation on the line side of the device.
12.2 Functional insulation alone is acceptable in a portable or cord-connected device where, in the event
that the functional insulation should fail, there would be no shock hazard at the ground-fault
circuit-interrupter.
AUGUST 27, 1993 GROUND-FAULT CIRCUIT-INTERRUPTERS - UL 943 14
12.3 In performing the evaluation described in 12.2 at a manual switch in the supervisory circuit
(described in 20.1), the device need not trip if the value of current available in the event that the functional
insulation of the switch should fail would not exceed the value of current employed by the supervisory
circuit.
12.4 The equivalent of functional insulation shall be interposed between the grounding conductor of the
power-supply cord and accessible parts of a cord-connected ground-fault circuit-interrupter. If such
insulation is inherent in a receptacle:
a) There shall be instructions visible when the receptacle is being removed for replacement to
replace the receptacle with only an identical replacement, and how to obtain the replacement, and
b) It shall not be possible to use a standard grounding-type receptacle as a replacement without
first performing a drilling or cutting operation.
12.5 The dielectric of a capacitor is not acceptable as supplementary insulation.
12.6 Except where specifically acceptable for the purpose, the jacket of the power-supply cord of the
ground-fault circuit-interrupter is not considered to provide insulation. See 16.5.
13 Accessibility of Energized Parts
13.1 Parts of a ground-fault circuit-interrupter shall not be accessible when they are energized.
13.2 In determining compliance with the provisions of 13.1:
a) Except at a contact of an attachment-plug receptacle, a part is considered to be accessible if
it can be touched with a 3/32-inch (2.4 mm) diameter rod.
b) A permanently connected device is to be mounted as intended.
c) A door or cover that can be opened or removed without the use of a separate tool is to be open
or removed, and
d) A door or cover that must be opened or removed in order to use a ground-fault
circuit-interrupter is to be opened or removed.
e) Material that is not acceptable as insulation is considered to be conductive.
13.3 Access to the trip mechanism and electronics of a portable ground-fault circuit-interrupter, not
intended to be repaired, shall not be attainable with ordinary tools. Access shall be limited by use of
tamper-resistant screws, rivets, welding or other equivalent means.
Added 13.3 effective July 4, 1998
14 Internal Wiring
14.1 The gauge and insulation of wires shall withstand the mechanical and electrical stresses of service.
Particular consideration should be given to the effect of vibration and user servicing where wire smaller
than No. 24 AWG is employed.
MARCH 24, 1997 GROUND-FAULT CIRCUIT-INTERRUPTERS - UL 943 15
14.2 In a cord-connected ground-fault circuit-interrupter, at a wire termination or splice there shall be at
least one independent means provided which alone could prevent the conductor from becoming free to
bridge supplementary or reinforced insulation in the event that the wire should break at the termination or
splice. A wire-binding screw or nut shall be suitably prevented from loosening such as with a spring-type
lockwasher or equivalent, if such loosening could allow the attached conductor to become free to bridge
supplementary or reinforced insulation.
14.3 Electrical splices, terminations, and the like shall provide effective, continuous conductivity.
14.4 In determining compliance of a clamped splice or termination with the provisions of 14.3,
consideration is to be given to the likelihood of permanent deformation under mechanical load (creep).
15 Field Wiring
15.1 A ground-fault circuit-interrupter intended for permanent connection to the branch circuit shall be
provided with means for the connection of wires having an ampacity in accordance with the National
Electrical Code, ANSI/NFPA 70, and, at least two equipment-grounding terminals. See 9.1.
15.2 In a permanently connected ground-fault circuit-interrupter, either:
a) Acceptable barriers shall be employed to separate load-circuit conductors and terminals from
terminals and conductors of any other circuit, or
b) All such parts shall be insulated for the maximum voltage of either circuit.
15.3 Lead-type terminals shall not differ by more than two wire sizes from the size referred to in 15.1,
providing that wire smaller in cross-section than No. 14 AWG shall not be used.
15.4 The insulation of lead-type terminals shall be for the intended purpose, such as 0.030-inch
(0.76-mm) thick minimum rubber or thermoplastic material.
15.5 A lead-type terminal shall be so constructed as to withstand the stress of normal handling without
damage to the ground-fault circuit-interrupter.
15.6 In order to determine compliance with the provisions of 15.5, each terminal lead is to withstand a
tensile force increased gradually to 20 lbf (89 N), and maintained at that value for five minutes.
15.7 Green coloring with or without one or more yellow stripes and white or natural grey coloring shall
not be used for the covering of a terminal lead unless intended for connection to grounding and grounded
conductors respectively. See also 39.2.6.
15.7 revised January 4, 1995
15.8 The free length of a terminal lead shall be at least 6 inches (152 mm).
15.9 A terminal connector shall be prevented from moving so as to strain factory connections or reduce
spacings to unacceptable values. Friction alone is not to be depended upon to prevent such movement.
15.10 At a terminal that is not considered to be a pressure terminal connector, it shall not be necessary
to assemble or adjust parts other than loosening or tightening a screw, bolt, or nut.
MARCH 24, 1997 GROUND-FAULT CIRCUIT-INTERRUPTERS - UL 943 16
15.11 A terminal connector of the wire-binding type may be used to terminate conductors no larger than
No. 10 AWG (5.3 mm 2 ).
15.12 In order to determine compliance with the provisions of 15.10, a wire-binding screw or nut is to be
tightened on a conductor selected in accordance with the provisions of 15.1 to a torque of 20 lbf-in (2.3
N·m) without causing displacement of the wire or damage to the terminal assembly or the wire. Except
where the configuration of the terminal assembly does not permit it, or markings allow the use of unformed
wire, the wire is to be formed into a 3/4 loop that will just be accommodated by the assembly, before
tightening.
SEPTEMBER 18, 2000 GROUND-FAULT CIRCUIT-INTERRUPTERS - UL 943 16A
MAY 13, 1998 GROUND-FAULT CIRCUIT-INTERRUPTERS - UL 943 16B
No Text on This Page
16 Power-Supply Cord
16.1 A cord-connected ground-fault circuit-interrupter shall be provided with not less than 6 ft (1.83 m) of
flexible cord and an attachment plug for connection to the supply circuit. The rating of the attachment plug
is to be equal to the rating of the ground-fault circuit-interrupter.
Exception: A ground-fault circuit-interrupter may be provided with less than 6 ft (1.83 m) of permanently
attached flexible cord or with a motor-attachment plug if the ground-fault circuit-interrupter is marked as
indicated in 38.3.3.
16.1 revised January 4, 1995
16.2 The flexible cord shall be of Type S, ST, SO, STO, SJ, SJT, SJO, or SJTO.
16.3 Strain on the power-supply cord that may occur by way of pulling, twisting, or pushing into the
ground-fault circuit-interrupter housing shall not be transmitted to cord-conductor terminations.
16.4 In order to determine that the strain of pulling on the supply cord will not be transmitted to the cord
terminations as provided in 16.3, a tensile force is to be applied to the cord and increased gradually to 35
lbf (156 N). The force is to be maintained at 35 lbf (156 N) for one minute.
16.5 A clamp or similar device of conductive material applied to the power-supply cord shall have
supplementary insulation interposed between the cord and the clamping device or shall not be accessible.
16.6 A surface of a ground-fault circuit-interrupter against which a flexible cord is likely to bear shall be
smooth and well-rounded.
16.7 Unless protection is provided in a ground-fault circuit-interrupter to prevent overloading of the
supply-cord conductors, the current rating of the supply cord shall not be less than the current rating of
the attachment plug on the supply cord.
16.8 The points within the ground-fault circuit-interrupter intended for the termination of
power-supply-cord conductors shall be plainly identified to show the proper connection of the conductors
of a replacement cord, and to indicate that the grounding conductor shall not be connected to accessible
metal parts of the unit. This marking is to be discernible only after access is obtained to the terminations,
except that if there is safe, convenient provision for cord replacement, reference to such replacement may
be discernible from outside the ground-fault circuit-interrupter also.
16.9 The attachment plug of a ground-fault circuit-interrupter shall be a molded-on type or shall have the
cord-conductor terminations sealed, or shall be provided with other means to prevent accidental contact
between the grounding conductor and either or both of the power conductors, within the attachment plug.
16.10 A portable ungrounded ground-fault circuit-interrupter shall be provided with a polarized attachment
plug cap.
16.11 If a 3-wire grounding-type attachment plug or a 2-wire polarized attachment plug is provided, the
attachment plug connections shall comply with Figure 16.1, and the polarity identification of the flexible
cord shall comply with Table 16.1.
JANUARY 4, 1995 GROUND-FAULT CIRCUIT-INTERRUPTERS - UL 943 17
This is generated text for figtxt.
Table 16.1
Polarity identification of flexible cords
Acceptable combinations
Method of identification
Wire intended to be
grounded b All other wires b
Color of braids on individual
conductors
A Solid white or natural gray –
without tracer
Solid color other than white or
natural gray – without tracer
B Color other than white or
natural gray, with tracer in
braid
Solid color other than white or
natural gray – without tracer
Color of insulation a on
individual conductors
C Solid white or natural gray Solid color other than white, or
natural gray
D Light blue Solid color other than light
blue, white
a
Only for cords having no braid on any individual conductor.
b
Wire finished to show a green color with or without one or more yellow stripes or tracers is to be used only as an equipment-
grounding conductor. See Figure 16.1
Figure 16.1
Connection to attachment plug
a
In the above illustration, the blade to which the green conductor is connected may have a U-shaped or circular cross section.
b
Signifies a conductor identified in accordance with Table 16.1 as wire intended to be grounded.
SEPTEMBER 18, 2000 GROUND-FAULT CIRCUIT-INTERRUPTERS - UL 943 18
17 Receptacles
17.1 A receptacle of a ground-fault circuit-interrupter shall be of the grounding type with the grounding
terminal conductively connected to the grounding conductor of the power-supply cord.
Exception: A portable ground-fault circuit-interrupter that is not provided with an equipment ground shall
not be provided with a receptacle or cord connector of the grounding type, but shall be provided with a
polarized receptacle or cord connector.
17.2 The ampere rating of the receptacle of a ground-fault circuit-interrupter that has only a single
receptacle shall be equal to the rating of the attachment plug of the supply cord.
17.3 The rating of any receptacle not having individual overcurrent protection, provided on a ground-fault
circuit-interrupter having more than one receptacle, shall be one of those shown in Table 17.1.
17.4 The face of a two-conductor ungrounded receptacle or cord connector shall obstruct the insertion of
a 2-pole 3-wire grounding type attachment plug cap.
Table 17.1
Receptacle current rating in amperes
Supply – Cord Cap Amperes 15 20 30
Receptacle 15 15 or 30
18 Spacings
18.1 Except at field-wiring terminals, the through-air and over-surface spacings between conductive parts
shall not be less than the values shown in Table 18.1.
18.2 The spacing shall not be less than 1/4 inch (6.4 mm) between field-wiring terminals not operating at
the same potential for devices rated up to 200 v peak, and 3/8 inch (9.5 mm) for devices rated up to 400
v peak.
18.3 Except as permitted in note c to Table 18.1, if a groove or a slot in insulating material is less than
1/64 inch (0.4 mm) wide, the contour of the slot or groove is to be disregarded in measuring spacings over
the surface.
18.4 Spacings measured along the boundary of insulating materials that have been joined together are
considered to be spacings over surface unless it can be shown that the dielectric strength of the boundary
is not less than that of any of the materials joined.
18.5 In determining compliance with the provisions of 18.1 or 18.2, parts not locked in position, parts
subject to random orientation (such as noncircular heads of screws), adjustable parts of terminal
connectors, and the like are to be moved to the most adverse position.
18.6 In determining spacings through openings in a housing of insulating material, metal foil may be used
to bridge the opening but is not to be pressed into the opening.
18.7 Film-coated magnet wire is considered to be uninsulated in determining spacings.
AUGUST 27, 1993 GROUND-FAULT CIRCUIT-INTERRUPTERS - UL 943 19
Table 18.1
Spacing in inches (mm) a,e
Table 18.1 revised May 13, 1998
Operating potential between parts
70 V peak or less 71 – 200 V peak 201 – 400 V peak
Through air Over surface Through air Over surface Through air Over surface
Parts
separated
by Open a
Closed–
in b Open a Closed–in b Open a
Closed–
in b Open a
Closed–
in b Open a
Closed–
in b Open a
Closed–
in b
Functional
insulation c
1/16 d
(1.6)
1/16 d
(1.6)
1/16 d
(1.6)
1/16 d
(1.6)
1/8 (3.2) 1/16
(1.6)
1/4
(6.4)
1/16 (1.6) 1/4 (6.4) 1/8 (3.2) 3/8 (9.5) 1/8 (3.2)
Supplementary
insulation
1/8 (3.2) 1/16
(1.6)
1/4 (6.4) 1/16
(1.6)
1/8 (3.2) 1/16
(1.6)
1/4
(6.4)
1/8 (3.2) 1/4 (6.4) 1/16 (1.6) 3/8 (9.5) 1/8 (3.2)
Double or
Reinforced
insulation
1/4 (6.4) 1/8 (3.2) 1/2
(12.7)
1/8 (3.2) 1/4 (6.4) 1/8 (3.2) 1/2
(12.7)
1/4 (6.4) 1/2
(12.7)
1/4 (6.4) 3/4 (19) 1/4 (6.4)
a
A space that is not specially protected from deposition of dirt.
b
A space that is specially from deposition of dirt; i.e., a sealed housing that meets the requirements of the dust test outlined in Section 37.
c
Smaller spacings may be acceptable where they are inherent in a suitable component.
d
May be less than 1/16 in (1.6 mm), but not less than 1/32 in (0.8 mm) at a printed wiring board without conformal coating.
e
For printed wiring boards with suitable conformal coating which has been determined to comply with the requirements for conformal coatings in the
Standard for Polymeric Materials – Use in Electrical Equipment Evaluations, UL 746C, spacings may be reduced to 1/32 in (0.8 mm), and may be
further reduced if the coating is determined to be suitable and a special dielectric withstand test is performed between the conductors.
MAY 13, 1998 GROUND-FAULT CIRCUIT-INTERRUPTERS - UL 943 20
18A Alternate Spacings - Clearances and Creepage Distances
Section 18A added September 18, 2000
18A.1 When applying requirements in Alternate Spacings - Clearances and Creepage Distances, Section
18A, as an alternative to the measurement method specified in Spacings, Section18, for functional
insulation, the minimum acceptable clearances (through air spacings) and creepage distances (over
surface spacings) for a printed wiring board assembly shall be evaluated as specified in 18A.2 – 18A.4
using the applicable requirements in the Standard for Insulation Coordination Including Clearances and
Creepage Distances for Electrical Equipment, UL 840.
18A.2 When applying the requirements in the Standard for Insulation Coordination Including Clearances
and Creepage Distances for Electrical Equipment, UL 840, the environment for a printed wiring board
assembly within a ground-fault circuit-interrupter is considered to be:
a) Pollution degree 3 for an assembly without a conformal coating, or
b) Pollution degree 2 for
i) an assembly with a conformal coating,
ii) an assembly without a conformal coating when the printed wiring board is contained
in a sealed housing that complies with the Dust Test, Section 37 or,
c) Pollution degree 1 for an assembly with a conformal coating complying with the Printed
Wiring Board Coating Performance Test in UL 840.
18A.3 When applying Clearance B (controlled overvoltage) construction requirements from the Standard
for Insulation Coordination Including Clearances and Creepage Distances for Electrical Equipment UL
840, the applicable overvoltage category for line voltage circuits is Category III for permanently connected
GFCIs and Category II for portable and cord connected GFCIs. Category I is applicable to low-voltage
circuits if a short circuit between the parts involved results in operation of the controlled equipment which
increases the risk of fire, the risk of electric shock, or both. Any overvoltage protection device needed to
achieve these categories shall be provided as an integral part of the ground-fault circuit-interrupter.
18A.4 Where measurement of clearances and creepage distances is involved to establish the minimum
spacings, the methods specified in Measurement of Clearance and Creepage Distances, Section 7, of the
Standard for Insulation Coordination Including Clearances and Creepage Distances for Electrical
Equipment UL 840, shall be used.
SEPTEMBER 18, 2000 GROUND-FAULT CIRCUIT-INTERRUPTERS - UL 943 21
19 Operating Mechanism
19.1 Compliance with the provisions of 24.1.1 – 24.1.4 shall not be prevented by manipulation or restraint
of accessible control levers, knobs, and the like of a ground-fault circuit-interrupter.
19.2 A ground-fault circuit-interrupter that has tripped in accordance with the provisions of 24.1.1 – 24.1.4
shall not be capable of automatic reclosure.
19.3 If a permanently connected ground-fault circuit-interrupter trips because of a loss of power on the
line side, it shall be capable of automatic reclosure when power is restored.
19.4 In a permanently connected ground-fault circuit-interrupter that cannot trip without power from the
line, the grounded circuit conductor shall be electrically continuous during normal operation of the device.
19.5 A 120/240 V ground-fault circuit-interrupter shall function to provide protection with one or both
ungrounded line terminals energized.
20 Supervisory Circuit
20.1 A ground-fault circuit-interrupter shall be provided with a supervisory circuit that will allow for
periodic, convenient testing of the ability of the device to trip by way of a ground fault.
20.2 If it is necessary to employ a separate tool in order to operate the supervisory circuit, operation is
considered not to be convenient within the intent of these requirements.
20.3 The supervisory circuit shall be connected to the grounded supply-circuit conductor and the
ungrounded load-circuit conductor.
20.4 The results of the test shall be made known by means of an audible or visible indication.
20.5 The current employed by the supervisory circuit shall be sufficient to cause tripping at 85 percent of
rated voltage, provided that at rated voltage the current shall not exceed 9 mA in a Class A device and
32 mA in a Class B device.
PERFORMANCE
21 General
21.1 A sample that has been struck as described in 10.1.5 or 10.1.8 and conditioned as described in 22.7
shall at any convenient time after removal from the conditioning atmosphere, and in the following order,
comply with the provisions of these requirements for voltage surge, high-resistance ground faults and
dielectric voltage withstand tests.
21.2 Except as noted in 21.1, a separate, unconditioned representative ground-fault circuit-interrupter
shall be subjected to each of the following tests.
Exception: The same representative device may be used for more than one test if agreeable to all
concerned.
21.2 added April 2, 1996
SEPTEMBER 18, 2000 GROUND-FAULT CIRCUIT-INTERRUPTERS - UL 943 22
22 Leakage Current Test
22.1 The leakage current of a ground-fault circuit-interrupter, when tested in accordance with 22.2 – 22.7,
shall be no more than 0.5 mA.
22.2 All accessible parts of a ground-fault circuit-interrupter are to be tested for leakage currents. The
accessible parts are to be tested individually, collectively, and from one part to another.
22.3 If a conductive surface other than metal is used for the enclosure or part of the enclosure, the
leakage current is to be measured using metal foil with an area of 10 by 20 cm in contact with the surface.
Where the surface is less than 10 by 20 cm, the metal foil is to be the same size as the surface. The metal
foil is not to be pressed into openings and is not to remain in place long enough to affect the temperature
of the sample.
22.4 The measurement circuit for leakage current of a cord-connected device is to be as shown in Figure
22.1. The measurement instrument is defined in items a – d of this paragraph. The meter that is actually
used for a measurement need only indicate the same numerical value for a measurement as would the
defined instrument. The meter used need not have all the attributes of the defined instrument.
a) The meter is to have an input impedance of 1500 ohms resistive shunted by a capacitance
of 0.15 µF.
b) The meter is to indicate 1.11 times the average of the full-wave rectified composite
waveform of voltage across the resistance or current through the resistance.
c) Over a frequency range of 0 – 100 kHz, the measurement circuitry is to have a frequency
response (ratio of indicated to actual value of current) that is equal to the ratio of the impedance
of a 1500-ohm resistance, shunted by a 0.15-µF capacitance, to 1500 ohms. At an indication of
0.5 mA, the measurement is to have an error of not more than five percent at any frequency
within the range of 0 – 100 kHz.
d) Unless the meter is being used to measure leakage from one part of the sample to another,
the meter is to be connected between the accessible parts and the ground supply conductor.
This is generated text for figtxt.
22.5 A permanently connected ground-fault circuit-interrupter is to be connected to the supply by way of
the terminals of the device, and tested in the same manner as a cord-connected device except that
switches S1 and S2 are not to be employed.
22.6 A sample of the ground-fault circuit-interrupter is to be tested for leakage current after the
conditioning described in 22.7. If removed from the humidity chamber, the testing is to start within one
minute after its removal. The grounding conductor of a cord-connected unit is to be open at the supply
receptacle and the grounding conductor of a permanently connected unit is not to be used. The supply
voltage is to be adjusted to 110 percent of the rated voltage. The test sequence, with reference to the
measuring circuit in Figure 22.1, is as follows:
a) With switch S1 open, the sample is to be connected to the measurement circuit. The
leakage current is to be measured using both positions of switch S2 and with the sample
switching devices in all their positions.
b) Switch S1 is then to be closed, energizing the sample, and within a period of five seconds,
the leakage current is to be measured using both positions of switch S2 and with the control
settings varied throughout the operating range.
SEPTEMBER 18, 2000 GROUND-FAULT CIRCUIT-INTERRUPTERS - UL 943 22A
c) Leakage current is to be monitored at intervals necessary to determine the maximum
leakage current, with additional measurements being taken until such time as thermal
equilibrium is attained. Both positions of switch S2 are to be used in determining this
measurement.
22.7 The conditioning mentioned in 22.6 and 21.1 is exposure to air at a relative humidity of 93 ±2 percent
at a temperature of 32.0 ±2.0°C (89.6 ±3.6°F). The ground-fault circuit-interrupter is to be exposed to
ambient air at a temperature of at least 30°C (86°F) until thermal equilibrium is attained before placed in
the test chamber. A rainproof device is to be kept in the chamber for 168 hours. Other devices are to be
kept in the chamber for 48 hours.
Figure 22.1
Leakage-current measurement circuits
SEPTEMBER 18, 2000 GROUND-FAULT CIRCUIT-INTERRUPTERS - UL 943 22B
23 Voltage Surge Test
23.1 The sample shall be subjected to the following surge voltage impulses in the order given:
a) Ten random applications or three controlled applications of a 6 kV surge impulse at 60
second intervals. Tripping of the ground-fault circuit-interrupter may result but there shall be no
fire or shock hazard.
b) Ten random applications or three controlled applications of a 3 kV surge impulse at 60
second intervals. Tripping of the ground-fault circuit-interrupter is not acceptable.
23.2 The sample is to be connected to a supply of rated voltage. The grounding lead or terminal of the
sample is to be connected to the supply conductor serving as the neutral. The sample is to be in the ″on″
condition with no load connected. For each application, the voltage is to have the specified initial peak
amplitude of 6 or 3 kV when applied to the 60 Hz supply to the unit under test. Each of the ten applications
is to be random with respect to the phase of the 60 Hz supply voltage. If three controlled applications are
employed, one application is to be at essentially zero of the supply voltage wave, one at positive peak and
one at negative peak.
23.2 revised September 18, 2000
23.3 The surge generator is to have a surge impedance of 50 ohms. When there is no load on the
generator, the waveform of the surge is to be essentially as follows:
a) Initial rise time, 0.5 microseconds between 10 percent and 90 percent of peak amplitude,
b) The period of the following oscillatory wave, 10 microseconds, and
c) Each successive peak, 60 percent of the preceding peak.
23.4 Figures 23.1 and 23.2 show a typical surge generator and control relay.
SEPTEMBER 18, 2000 GROUND-FAULT CIRCUIT-INTERRUPTERS - UL 943 23
SEPTEMBER 18, 2000 GROUND-FAULT CIRCUIT-INTERRUPTERS - UL 943 24
No Text on This Page
Figure 23.1
Surge generator circuit
Figure 23.1 revised May 13, 1998
C1 = 0.025 µF, 10 Kv R1 = 22 Ohms, 1 W, composition
C2 = 0.01 µF, 10 Kv R2 = 12 Ohms, 1 W, composition
C3 = 4 µF, 400 v R3 = 1.3M Ohms (12 × 110X Ohms, 1/2 W)
R4 = 47K Ohms (10 × 4.7 Ohms, 1/2 W)
L1 = 15 µH [23 turns, No. 23 AWG wire, 0.7 inch (18
mm) diameter air core]
R5 = 200 Ohms, 1/2 W
L2 = 70 µH [28 turns, No. 23 AWG wire, 2.6 inch (66
mm) diameter air core]
CR–1 = Relay
MAY 13, 1998 GROUND-FAULT CIRCUIT-INTERRUPTERS - UL 943 25
Figure 23.2
Relay control circuit for surge generator
Figure 23.2 revised May 13, 1998
R1 = 10K Ohms, 1 W
R2 = 1K Ohms, 1/2 W
R3 = 1K Ohms, 1/2 W
C1 = 32 µF, 250 V
D1 = IN5060 or equivalent
D2 = IN5060 or equivalent
SCR1 = GE C122B or equivalent
CR–1 = Relay GE CR 2790 E 100 A2 or equivalent
T1 = Triad N4S X or equivalent
MAY 13, 1998 GROUND-FAULT CIRCUIT-INTERRUPTERS - UL 943 26
24 High-Resistance Ground Faults Test
24.1 General
24.1.1 A Class A ground-fault circuit-interrupter shall be capable of interrupting the electric circuit to the
load when the fault current to ground I is within the range of 6 – 264 mA within the time interval T in
accordance with the relationship:
in which T is expressed in seconds and I is expressed in milliamperes.
24.1.2 A Class B ground-fault circuit-interrupter shall be capable of interrupting the electric circuit to the
load when the fault current to ground I is within the range of 20 – 1,056 mA within the time interval T in
accordance with the relationship:
in which T is expressed in seconds and I is expressed in milliamperes.
24.1.3 The trip times indicated in 24.1.1 and 24.1.2 correspond to a maximum nominal voltage to ground
of 125 V.
24.1.4 A cord-connected ground-fault circuit-interrupter shall comply with the provisions of 24.1.1 with
and without one or more of the following defects in its power-supply cord:
a) The ungrounded and grounded conductors transposed at the attachment plug terminals.
b) An open circuit in the grounding conductor.
c) An open circuit in any one power conductor.
d) Except if normal operation of the supervisory circuit would provide an indication of trouble, the
ungrounded and grounding conductors of the power-supply cord transposed at the attachment
plug terminals.
24.1.5 In order to determine compliance with the provisions of 24.1.1 – 24.1.4, a ground-fault
circuit-interrupter is to be connected as shown in Figure 24.1 and tested as described in 24.2.1, in the
sequence of steps described in Table 24.2.
MAY 13, 1998 GROUND-FAULT CIRCUIT-INTERRUPTERS - UL 943 26A
Figure 24.1
High-resistance ground-fault test circuit
Figure 24.1 revised May 13, 1998
S 4 – Integral on-off or other operating switch (not test switch)
MAY 13, 1998 GROUND-FAULT CIRCUIT-INTERRUPTERS - UL 943 26B
24.2 High-resistance ground fault test
24.2.1 In performing the test mentioned in 24.1.5, the resistance R B is to be varied to obtain the test
values of current to be indicated by meter A. The sum of R B and the resistance of meter A is to be not
less than (1) 500 ohms for a Class A and for a cord-connected ground-fault circuit-interrupter, and (2) 125
ohms for a Class B ground-fault circuit-interrupter. The test values of current are to include the minimum
specified and the maximum possible according to the class and one or two additional values as may be
considered necessary to assure compliance with the provisions of 24.1.1 – 24.1.4. Ten measurements of
current duration are to be made for each mode of operation described and for each value of test current
selected. The average of each group of ten is not to exceed the time allowed for the rated class. Individual
measurements may exceed the time allowed for the rated class provided that such measurements do not
exceed 125 percent of the time allowed for the rated class. The modes of operation noted in Table 24.1
are to be performed. For ground-fault circuit-interrupters intended to be used on 120/240 V circuits, the
resistance is to be connected between each ungrounded load terminal, in turn, and the grounded
conductor of the supply.
Table 24.1
Modes of operation
Table 24.1 revised April 2, 1996
Precondition of circuit Action that starts ground-fault current
A Switch S 1 closed
Switch S 2 closed
Switch S 3 closed
Switch S 4 open
Switch S 4 is to be moved (1) in one
continuous motion to its extreme
position, and (2) to the position at which
the current just starts, and the operating
handle held in that position.
B Switch S 1 open Switch S 1 closed.
Switch S 2 closed
Switch S 3 closed
Switch S 4 closed
C Switch S 1 closed Switch S 2 closed.
Switch S 2 open
Switch S 3 closed
Switch S 4 closed
D Switch S 1 closed Switch S 3 closed a .
Switch S 2 closed
Switch S 3 open
Switch S 4 closed
a
In obtaining the minimum value of current specified for the rated class, R B is to be (1) decreased gradually until tripping
occurs, and (2) preset for the desired value.
24.2.2 It may be necessary to prevent tripping of the device under test while adjusting for various values
of current in resistance R B . Care should then be taken to assure that components that are not
continuously energized in normal operation should not be caused to be continuously energized during the
adjustment procedure. Attempts to bypass one or more poles of the device will usually produce the
condition described.
SEPTEMBER 18, 2000 GROUND-FAULT CIRCUIT-INTERRUPTERS - UL 943 27
24.2.3 In determining the ″most adverse″ conditions mentioned in Table 24.2, each of the operating
parameters described in items a – e of this paragraph is to be varied so as to obtain a combination, if any,
considered to be most adverse to the tested function of the ground-fault circuit-interrupter, at
room-temperature ambient. The ″most adverse″ condition of an operating parameter is to be learned from
(1) a study of the design and, (2) if necessary, from operating the sample, provided that if it is necessary
to operate the sample, that sample need not be subjected to any of the tests described in these
requirements.
a) LINE VOLTAGE – The closed-circuit line voltage is to be adjusted within the range of 85 – 110
percent of rated voltage, at rated load, with the cover(s), if any, of the device closed, and with the
device supported in its marked mounting position. If no mounting position is marked on the device,
any one position that is considered normal for the device is to be arbitrarily selected. The line
voltage to the device is to be obtained from a source having sinusoidal waveform and free from
any measurable transient voltage rises or dips.
b) MOUNTING POSITION – Except for a permanently connected ground-fault circuit-interrupter
marked to specify a mounting position, the device is to be placed in different positions. The
mounting position of a permanently connected device that is marked to specify a mounting
position is to be varied from the marked mounting position by no more than 10 degrees (for a total
range of 20 degrees). Rated load is to be connected and the cover(s), if any, of the device are to
be closed.
c) COVER POSITION – Any cover or door normally moved or removed during operation or
functioning of the device, or that can be moved or removed without the use of a tool, may be so
moved or removed. Rated load is to be connected.
d) LOAD – The load may have any value of current up to rated and is to be resistive.
e) GROUNDING – A cord-connected device, and a permanently connected device not marked to
indicate that it must be grounded, may be either grounded or ungrounded, whichever is more
adverse.
AUGUST 27, 1993 GROUND-FAULT CIRCUIT-INTERRUPTERS - UL 943 28
Table 24.2
Test sequence for high–resistance ground faults and false tripping
Ambient air temperature a Operating parameters Remarks
1. 25.0 ±5.0°C No voltage applied Establish thermal equilibrium with at least two hours of exposure.
(77.0 ±9.0°F) Do not test.
2. 25.0 ±2.0°C Most adverse Test per 24.1.5 and 25.2 as soon as possible to minimize self-
heating.
(77.0 ±3.6°F)
3. b 66.0 ±2.0°C Rated voltage and Establish thermal equilibrium with at least two hours of exposure.
(150.8 ±3.6°F) current Do not test.
4. b 66.0 ±2.0°C Most adverse Test per 24.1.5 and 25.2.
(150.8 ±3.6°F)
5. c 40.0 ±2.0°C Rated voltage and Establish thermal equilibrium with at least two hours of exposure.
(104.0 ±3.6°F) current Do not test.
6. c 40.0 ±2.0°C Most adverse Test per 24.1.5 and 25.2.
(104.0 ±3.6°F)
7. 25.0 ±5.0°C No voltage applied Establish thermal equilibrium with at least two hours of
(77.0 ±9.0°F) exposure. Do not test.
8. -35.0 ±2.0°C No voltage applied Establish thermal equilibrium with at least two hours of
(-31 ±3.6°F) exposure. Do not test.
9. -35.0 ±2.0°C Most adverse Tests per 24.1.5 and 25.2 as soon as possible to minimize
(-31 ±3.6°F) self-heating
10. d -5.0 ±2.0°C No voltage applied Establish thermal equilibrium with at least two hours of
(23 ±3.6°F) exposure. Do not test.
11. d -5.0 ±2.0°C Most adverse Tests per 25.2 as soon as possible to minimize
(23 ±3.6°F) self-heating
12. 25.0 ±5.0°C Rated voltage and Establish thermal equilibrium with at least two hours of
(77.0 ±9.0°F) current exposure. Do not test.
13. 25.0 ±5.0°C Most adverse Test per 24.1.5 and 25.2
(77.0 ±9.0°F)
a
The ambient air temperature is to be changed to each value shown without intentional delay.
b
In the event that a ground-fault circuit-interrupter is self-protecting such that it trips at this ambient temperature, lower values
of load current are to be employed, until the device just continues to operate, if possible.
c
This test is not to be performed if steps 3 and 4 have been performed employing rated current.
d
This test is not to be performed if product does not trip with less than 4 mA in step 9.
SEPTEMBER 18, 2000 GROUND-FAULT CIRCUIT-INTERRUPTERS - UL 943 29
24.2.4 A ground-fault circuit-interrupter shall comply with the provisions of 24.1.1 – 24.1.4 when the circuit
conductor that is normally grounded at the service only, is also grounded at a point in the load circuit of
the ground-fault circuit-interrupter.
24.2.5 In determining compliance with the provisions of 24.2.4, the sample is to be connected as shown
in Figure 24.2 and tested as described in 24.2.7 for each combination of R N and R G as indicated in Table
24.3. The tests are to be conducted both with R L open and with R L adjusted for rated current.
This is generated text for figtxt.
Figure 24.2
Supplementary high-resistance test circuit
Figure 24.2 revised May 13, 1998
MAY 13, 1998 GROUND-FAULT CIRCUIT-INTERRUPTERS - UL 943 30
24.2.6 When testing as described in 24.2.7, additional values of current indicated by meter A and in
resistance R L and other values of resistances R N and R G may be employed if necessary to determine
compliance with the provisions of 24.2.4. Such other values are to be in accordance with the rating of the
product and the cable constructions represented in Table 24.3. The product is to trip within the time
interval prescribed in 24.1.1 or 24.1.2.
24.2.7 The sample is to be tested following the procedure indicated in items a – c.
a) Close switch S1 and then switch S3. If the device does not trip, adjust resistance R B to any
value that will not cause tripping and close switch S2. Decrease resistance R B until meter A
reads 20 mA for a Class B device or 6 mA for other than a Class B device or the device trips.
The device may trip with meter A indicating less than the specified values of current. Conduct
procedures ten times.
b) Close switch S3 and then switch S1. If the device does not trip, adjust resistance R B to any
value that will not cause tripping and close switch S2. Decrease resistance R B until meter A
reads 20 mA for a Class B device or 6 mA for other than a Class B device or the device trips.
The device may trip with meter A indicating less than the specified values of current. Conduct
procedures ten times.
SEPTEMBER 18, 2000 GROUND-FAULT CIRCUIT-INTERRUPTERS - UL 943 30A
MAY 13, 1998 GROUND-FAULT CIRCUIT-INTERRUPTERS - UL 943 30B
No Text on This Page
c) With resistance R B adjusted to cause 20 mA for a Class B device or 6 mA for other than a
Class B device, close switches S2 and S3. Close switch S1. Conduct procedures ten times.
Table 24.3
Resistance in OHMS a
Table 24.3 revised September 3, 1996
AWG copper wire size of field wiring b
Combi-
nation Nos. 14 – 12 No. 10 No. 8
No. 6 No. 4
R N R G R N R G R N R G R N R G R N R G
1 0.008 0.008 0.005 0.005 0.0032 0.0032 0.002 0.002 0.0013 0.0013
2 0.08 0.20 0.05 0.13 0.0320 0.0833 0.021 0.053 0.013 0.0337
3 0.4 1.0 0.25 0.65 0.1601 0.4163 0.103 0.267 0.065 0.168
4 0.008 0.032 0.005 0.028 0.0032 0.0179 0.0021 0.0115 0.0013 0.0073
5 0.08 0.32 0.05 0.28 0.0320 0.179 0.021 0.115 0.013 0.073
6 0.4 1.6 0.25 1.4 0.1601 0.897 0.103 0.574 0.065 0.363
a
The combinations shown represent discrete lengths and constructions of cable or flexible cord. Resistances R N and R G
represent respectively the resistance of the grounded and the grounding conductors of the cable or cord.
b
See paragraph 14.1.
25 Resistance to False Tripping Test
25.1 A ground-fault circuit-interrupter shall have necessary resistance to tripping when connected to load
circuits that have:
a) Values of leakage current anticipated in normal service, and
b) Normal transient electrical disturbances such as those caused by switching.
25.2 In order to determine compliance with the provisions of 25.1, a ground-fault circuit-interrupter is to
be connected as shown in Figure 25.1 with the impedance Z described in 25.3 or 25.4, and tested as
described in (1) 25.6, in each of the steps shown in Table 24.2 and (2) 25.7. Switches S1 and S2 shown
in Figure 25.1 are to be of the mercury-contact type or otherwise capable of (1) closing with minimum
contact bounce and (2) opening with minimum clearing time. They may control both conductors if that is
more adverse.
25.3 With a Class B ground-fault circuit-interrupter, the impedance Z indicated in Table 25.1 is to be
employed.
SEPTEMBER 3, 1996 GROUND-FAULT CIRCUIT-INTERRUPTERS - UL 943 31
Table 25.1
Impedance
Table 25.1 revised January 4, 1995
Components of Z
Class B
Marked length a of conductor run in
feet (meters) Minimum resistance in ohms Capacitance in microfarads
Not over 100 (30) 20,000 0.010 or none
Over 100 but not over 150 (46) 13,300 0.015 or none
Over 150 but not over 175 (53) 11,400 0.0175 or none
Over 175 but not over 200 (61) 10,000 0.020 or none
Over 200 but not over 250 (76) 8,000 0.025 or none
a
Marked length to comply with the provisions of 39.2.3 item 2. The length of conductor run is the total one-way length of the
conductors from the ground-fault circuit interrupter at every part of the load circuit. This is generated text for figtxt.
Figure 25.1
False-tripping test circuit
JANUARY 4, 1995 GROUND-FAULT CIRCUIT-INTERRUPTERS - UL 943 32
25.4 With a device other than Class B, the components of impedance Z are to be as indicated in Table
25.2.
Table 25.2
Impedance (Z)
Components of Z
Ground–fault circuit–interrupter Resistance in ohms Capacitance in microfarads
Plug Connected 80,000 0.012 or none
Class A 64,000 0.015 or none
25.5 A ground-fault circuit-interrupter with an adjustable control shall comply with the provisions of 25.1
for at least one setting of the control.
25.6 The tests mentioned in 25.2 are as follows:
a) Under the ″most adverse″ conditions described in 25.9, the device is not to trip while operating
continuously,
b) Under the ″most adverse″ conditions described in 25.9, the device is not to trip more than
three times in ten operations of each switch S1 and switch S2, and
c) Under the ″most adverse″ conditions described in 25.9, a device other than Class B is not to
trip at less than 4 mA. The device may trip at less than 4 mA but not less than 3.5 mA when the
temperature of the ambient air is less than minus 5°C (plus 23°F) or more than 40°C (104°F). The
impedance Z is gradually reduced until the ground-fault circuit-interrupter trips. The capacitive
component of Z is to be disconnected and switches S1 and S2 are to be closed. The procedure
is to be conducted three times under each of the ″most adverse″ conditions.
25.7 The tests mentioned in 25.2 are as follows:
a) Under the ″normal″ conditions described in 25.8, the device is not to trip more than three times
in 100 operations of each switch S1 and S2, and
b) Under the ″normal″ conditions described in 25.8, the device is not to trip more than one time
in ten operations of any switch that is an integral part of the device and that controls the electric
supply to the load.
25.8 Normal conditions called for in 25.7 are to include rated voltage, ground-lead switch S G closed,
normal mounting position, all doors closed and rated load. The voltage waveform is to be sinusoidal and
free from any measurable transient rises or dips.
25.9 In determining the ″most adverse″ conditions mentioned in Table 24.2, each of the operating
parameters described in items a – f of this is to be varied so as to obtain a combination, if any, considered
to be most adverse to the tested function of the ground-fault circuit-interrupter, at room temperature
ambient. The most adverse condition of an operating parameter is to be learned from (1) a study of the
design and, (2) if necessary from operating the sample, provided that if it is necessary to operate the
sample, that sample need not be subjected to any of the tests described in these requirements. An
adjustable control, if provided, is not to be adjusted after having started the tests specified in 25.2.
AUGUST 27, 1993 GROUND-FAULT CIRCUIT-INTERRUPTERS - UL 943 33
a) LINE VOLTAGE – The voltage is to be adjusted within the range of 85 – 110 percent of rated
voltage, with the covers (if any) of the device closed, and with the device supported in its marked
mounting position. If no mounting position is marked on the device, any one position that is
considered normal for the device is to be arbitrarily selected. The line voltage to the device is to
be obtained from a source having sinusoidal waveform and free from any measurable transient
voltage rises or dips.
b) MOUNTING POSITION – Except for a permanently connected ground-fault circuit-interrupter
marked to specify a mounting position, the device is to be placed in different positions. The
mounting position of a permanently connected device which is marked to specify a mounting
position is to be varied from the marked mounting position by no more than 10 degrees (for a total
range of 20 degrees). Rated load is to be connected and the cover(s), if any, of the device are to
be closed.
c) COVER POSITION – Any cover or door normally moved or removed during operation or
functioning of the device, or that can be moved or removed without the use of a tool, may be so
moved or removed. Rated load is to be connected.
d) LOAD – The load may have any value of steady-state current up to rated. For a Class A
device, the load may be appliances, tools, underwater swimming-pool lighting fixtures or other
utilization equipment. For a Class B device, the load is to be underwater swimming-pool lighting
fixtures or the equivalent. See 32.8.
e) CAPACITIVE LEAKAGE – The value of capacitance (selected from Table 25.1) may be
connected or omitted.
f) GROUNDING – If a permanently connected device is not marked to indicate that it must be
grounded, ground-lead switch SG may be open or closed.
26 Resistance to Environmental Noise Test
26.1 A ground-fault circuit-interrupter shall resist tripping from the effects of an RF signal varied from
10-450 MHz and function properly when tested in accordance with 26.2 – 26.5.
26.2 The test circuit for environmental electrical noise is to be as shown in Figure 26.1. The test
equipment is defined in Items a – d of this paragraph.
a) RF Signal Generator
Frequency Range: 10 to 450 MHz min
Accuracy: ±3% after warm-up
Modulation: Continuous Wave (CW)
Adjustable Output Attenuator
Spectral Purity:
Harmonic distortion (output power ± + 3 dBm): <−20 dBc.
AUGUST 27, 1993 GROUND-FAULT CIRCUIT-INTERRUPTERS - UL 943 34
Spurious output signals, subharmonically and nonharmonically related (excluding
line related): <−100 dBc.
Residual AM (average rms): −55 dBc in a 50 Hz to 15 kHz post-detection noise
bandwidth.
Residual FM on CW (averaged rms deviation): <0.3 ppm in a 0.3 to 3 kHz post-detection
noise bandwidth: <0.5 ppm in a 50 Hz to 15 kHz post-detection noise bandwidth.
Output Voltage: Is to be capable of delivering 0.5 V rms min across a 51 ohm resistive
load.
b) High Frequency Voltmeter
Frequency Range: 10 to 450 MHz min
Voltage Range: Is to have a range suitable for measuring a value of 0.5 V rms to an
accuracy of ±3%.
Input Impedance: >10M ohm shunted by 1.5 pF or less capacitance.
c) RF Coupling Fixture
The RF coupling fixture is to be constructed in accordance with Figure 26.2. Modifications
to the Coupling Fixture which may be required by the product configuration are to comply
with 26.3. The bill-of-materials for the fixture appears in Table 26.1.
d) Isolation Transformer
Secondary Voltage: Rated voltage for the GFCI under test.
Frequency: 50/60 Hz
VA: 225 min
Triad-Utrad N55M or equivalent
APRIL 2, 1996 GROUND-FAULT CIRCUIT-INTERRUPTERS - UL 943 35
Figure 26.1
Environmental electrical noise test schematic diagram
AUGUST 27, 1993 GROUND-FAULT CIRCUIT-INTERRUPTERS - UL 943 36
Figure 26.2
RF coupling fixture
APRIL 15, 2002 GROUND-FAULT CIRCUIT-INTERRUPTERS - UL 943 37
Table 26.1
Bill of materials
Item Material or part no. All dimensions in inches (mm) Reference Qty. Description
1 Lexan 8.75 × 6.12 × .50 (222 × 155 × 12.7) Base
2 Copper, 8.75 × 6.12 × 0.31 (222× 155 × 0.8) Base Plate
3 Copper, .075 (1.9) Thick Stab
4 .170 dia × .400 (4.3 × 10.2) L1 & L2 2 Coil 47 µh
5 #6–40 × 0.37 (3.5 – 0.5) Long Screw and Nut
6 Copper Terminal Solder
7 Aluminum, 2.26 × 2.00 × 1.60 (66.5 × 50.8 × 40.6) Lug Box
8 Quick disconnect terminal 2 Terminal Lug
9 3 AMP/125V S.B. 2 Fuse
10 #10–32 (4.8 – 0.08) 2 Mounting Screw
11 120V Polarized Plug & Cord (2 Wire)
12 Fuse Block Fuse Block (2 Fuse)
13 Rubber 2 Grommet
14 RG–58 C/U Coaxial Cable × 13 (330) Long Wire
15 BNC Connector, Male 2 Coax Connector (Male)
16 0.1 µf/1 kV Ceramic Disc C1, C2 2 Capacitor
17 Aluminum Bracket
18 51 ohm 1 W Carbon Composition R1 Resistor
19 .005 µf/1 kV C3 Capacitor
20 Brass .25–20 × .75 (6.35 – 20 × 19.1) Long Screw
21 2.75 × 2.15 × 1.65 Cover, Box
22 Fast clamp Terminal
23 #8 × 0.37 (4.2 × 9.5) Long 4 Screw
24 #8 × 0.50 (4.2 × 12.7) Long Screw
25 Aluminum, 1.75 × .540 × .070 (45.2 × 13.7 × 1.8) Hold down for Breaker Type
GFCI
26 #10–32 (4.8 – 0.8) Screw
27 #8 (4.2) Solder Lug
28 BNC Connector, Female Coax Connector (Female)
29 125V, 1/3 W Neon Light & Clip
30 2–Pole 125V, Normally Open S1 Momentary Switch
26.3 If the ground-fault circuit-interrupter contains integral wire connections, they are not to be shortened,
lengthened, or altered in any way when connected to the test equipment. GFCI’s employing field wiring
terminals are to be connected to the fixture with No. 14 AWG (2.1 mm 2 ) solid wire leads, 6 ±1/2 inches
(152 ±13 mm) long.
26.4 Prior to initiation of the test, the signal generator and amplifier are to warm up and stabilize.
SEPTEMBER 18, 2000 GROUND-FAULT CIRCUIT-INTERRUPTERS - UL 943 38
26.5 The test sequence, with reference to the test circuit in Figure 26.1, is as follows:
a) With switch S1 open, the line terminals of the test GFCI are to be connected to the test
fixture of Figure 26.2, observing proper polarity.
b) Set the signal generator to the first test frequency. Connect the voltmeter to the voltmeter
test point. The GFCI under test is to be in the ″tripped″ or ″off″ position while setting up the RF
Voltage to prevent loading effect on the RF generator. (If necessary the test GFCI may be
removed from the test fixture while setting the RF voltage).
c) Adjust the output of the amplifier until the voltmeter reads 0.5 V rms ±5%. Disconnect the
voltmeter from the voltmeter test point.
d) Turn ″on″ or reset the GFCI under test. Close switch S1 to apply rated voltage to the GFCI.
The GFCI’s shall not trip for a period of 30 s after application of the ac voltage and RF signal.
e) Depress the test switch to energize the supervisory circuit of the GFCI under test. The GFCI
shall trip.
f) Open switch S1, and set the signal generator to the next test frequency given in Table 26.2.
Repeat steps b – e until the GFCI has been evaluated at each of the test frequencies given in
Table 26.2.
Table 26.2
Test frequencies
Test no. Frequency mHz ± 5 percent
1 10
2 12
3 14
4 18
5 20
6 25
7 30
8 35
9 45
10 50
11 60
12 75
13 90
14 100
15 120
16 150
17 175
18 200
19 250
20 300
SEPTEMBER 18, 2000 GROUND-FAULT CIRCUIT-INTERRUPTERS - UL 943 39
Table 26.2 Continued on Next Page
Table 26.2 Continued
Test no. Frequency mHz ± 5 percent
21 350
22 450
27 Regulation Test
27.1 The inherent regulation of a ground-fault circuit-interrupter at rated input voltage shall be such that
the difference between output voltage at no load and output voltage at maximum rated current shall not
be more than two percent of the output voltage at rated current.
28 Normal Temperature Test
28.1 When carrying rated current and with rated voltage applied, a ground-fault circuit-interrupter shall not
attain a temperature at any point that is sufficiently high to (1) constitute a fire hazard, (2) affect injuriously
any materials used in the device, or (3) exhibit greater rises in temperature at specific points than
indicated in Table 28.1, based on an assumed average ambient temperature in normal service of 25°C
(77°F). A 120/240 V ground-fault circuit-interrupter is to be connected to a 120/240 V supply, or two
phases of a 120/208 V supply, adjusted to rated voltage of the supply. Loads are to be connected to the
load terminals to cause the load conductors, including the neutral conductor, to carry rated current.
28.2 In performing the test described in 28.1, parts and circuits that are heated only when there is
ground-fault current are to be continuously heated by providing a value of ground-fault current just low
enough not to cause tripping.
28.3 Coil or winding temperatures are to be measured by thermocouples unless access cannot be gained
for mounting a thermocouple (for example, a coil enclosed in sealing compound) or unless the coil wrap
includes thermal insulation, such as asbestos, or more than two layers (1/32 inch or 0.8 mm maximum)
of cotton, paper, rayon, or the like. At a point on the surface of a coil where the temperature is affected
by an external source of heat, the temperature rise measured by means of a thermocouple may be 10°C
(18°F) more than the indicated maximum, provided that the temperature rise of the coil, as measured by
the resistance method is no more than that specified in Table 28.1.
28.4 Except at coils, temperature readings are to be obtained by means of thermocouples consisting of
wires not larger than No. 24 AWG, and a temperature is considered to be constant when three successive
readings, taken at intervals of 10 percent of the previously elapsed duration of the test, but not less than
5-minute intervals, indicate no change. When thermocouples are used in the determination of
temperatures in connection with the heating of electrical devices, it is common practice to employ
thermocouples consisting of No. 30 AWG iron and constantan wires and a potentiometer type of indicating
instrument. Such equipment is to be used whenever referee temperature measurements by
thermocouples are necessary.
28.5 Ambient air is to be at any convenient temperature within the range of 20 – 30°C (68 – 86°F).
28.6 The thermocouples and related instruments are to be accurate and calibrated in accordance with
accepted laboratory practice. The thermocouple wire is to conform with the requirements specified in the
Initial Calibration Tolerances for Thermocouples table in ″Temperature-Measurement Thermocouples″,
ANSI/ISA MC96.1(1982).
28.6 revised September 18, 2000
SEPTEMBER 18, 2000 GROUND-FAULT CIRCUIT-INTERRUPTERS - UL 943 40
Table 28.1
Maximum acceptable temperature rises
Table 28.1 revised May 13, 1998
Materials and components
Degrees
C F
1. Varnished–cloth insulation 60 108
2. Fuses 65 117
3. Fiber employed as electrical insulation 65 117
4. Wood and other combustible material 65 117
5. Surfaces likely to contact the insulation of field wiring 35 63
6. A surface upon which a permanently wired unit might
be mounted in service and surfaces that might be
adjacent to the unit when it is so mounted
65 117
7. Class 105 insulation systems on windings of coils:
Thermocouple method 65 a 117 a
Resistance method 75 a 135 a
8. Molded phenolic composition 100 b 180 b
9. Rubber– or thermoplastic–insulated wires and cords 35 b 63 b
10. Accessible surfaces 35 63
11. Semiconductor junction c c
12. Electrolytic capacitor d 40 72
a
See 28.3
b
The limitations on phenolic composition and on rubber and thermoplastic insulations do not apply to compounds that have
been found suitable for higher temperatures.
c
The temperature T J at a semiconductor junction is related to the power P J dissipated at the junction, the thermal resistance
K TH from the junction to the cooling medium (generally, the specifications for the semiconductor device will include the thermal
resistance), and the temperature T M of that cooling medium, as shown:
T J = T M + (K TH ) P J
d
A capacitor operating at a higher temperature may be accepted on the basis of its marked temperature rating.
29 Dielectric Voltage-Withstand Test
29.1 In a ground-fault circuit-interrupter, except as described in 29.2, the insulation and spacings between
(1) line-connected circuits, and (2) other circuits and accessible parts shall withstand without breakdown
the test potentials shown in Table 29.1. The functional insulation and spacings of other circuits too shall
withstand without breakdown the test potentials shown in Table 29.1, except that where the potential does
not exceed 70 V peak in normal service, the test potential is to be 500 V. See 21.1.
SEPTEMBER 18, 2000 GROUND-FAULT CIRCUIT-INTERRUPTERS - UL 943 41
Table 29.1
Dielectric voltage–withstand
Insulation tested Potential (Volts)
Functional 1500a
Supplementary 2500
Reinforced 4000
a
900 V across the dielectric of a capacitor.
29.2 Functional insulation and spacings inherent in a component need not withstand the test potentials
mentioned in 29.1 if the component in question complies with the requirements applicable to the
component.
29.3 In order to determine compliance with the provisions of 29.1, the insulation and spacings are to be
subjected to 60 Hz essentially sinusoidal potentials increased from zero to the values specified and
maintained for a period of one minute. The increase in the applied potential is to be at a substantially
uniform rate and as rapid as is consistent with the value of the applied potential being correctly indicated
by the voltmeter.
29.4 Where the construction of the ground-fault circuit-interrupter is such as to deny access to the
insulation to be tested, suitable subassemblies may be employed.
29.5 In the application of test potentials to insulating surfaces, metal foil may be used providing that care
is taken to avoid flashover at the edge of the insulation.
30 Overload and Motor Starting Test
30.1 A ground-fault circuit-interrupter shall have necessary interrupting capacity. In addition, a Class A
and a cord-connected device shall not trip as a result of motor starting.
30.2 In order to determine compliance with the provisions of 30.1, a Class A or a cord-connected device
is to be caused to switch an inductive impedance adjusted for a value of load current equal to six times
the ampere rating of the device and a power factor within the range of 0.45 – 0.50.
30.3 Reactive components of the impedance mentioned in 30.2 may be paralleled with each other if they
are of the air-core type. An air-core reactor is to be paralleled with resistance adjusted to dissipate
approximately one percent of the total power dissipated in the impedance without such resistance.
30.4 The value of paralleled resistance R in ohms mentioned in 30.3 may be obtained by calculation from
the relationship in which E is the closed-circuit voltage at the load and I is the load current in amperes,
without resistance R.
SEPTEMBER 18, 2000 GROUND-FAULT CIRCUIT-INTERRUPTERS - UL 943 42
30.5 The supply circuit for the test mentioned in 30.2 is to have the capacity to provide a closed-circuit
voltage not less than 85 percent of the rated voltage of the ground-fault circuit-interrupter. Except when a
higher value is agreed to by those concerned, the open-circuit voltage is to be in the range of 100 – 105
percent of the rated voltage of the ground-fault circuit-interrupter. A 1-A fuse is to be connected between
the grounded conductor of the supply circuit and accessible conductive parts of the ground-fault
circuit-interrupter. This fuse shall not operate to open the circuit.
30.6 In performing the test mentioned in 30.2 the device is to be switched ″on″ and, after one second,
switched ″off″, for a total of 25 cycles of operation, at the rate of six cycles per minute.
Exception No. 1: If the device operation will not permit these cycle times, times as close as possible to
these are to be used.
Exception No. 2: If it is determined that for a duration less than one second, (1) the device conducts the
test current without interrupting the circuit or being adversely affected by heat, and (2) the device contacts
are properly seated before the break is initiated as confirmed by oscilloscopic or oscillographic
measurements, the ″ on ″ time may be reduced to that duration, provided the duration is not less than
one-half second.
30.7 A Class B ground-fault circuit-interrupter is to be caused to switch 25 times a tungsten-filament lamp
load, or the equivalent, adjusted for 150 percent of rated current. The number of lamps is to be the
smallest possible, using lamps of standard wattage ratings, providing that no lamp used is to be rated
more than 500 W without the agreement of the submitter. The ground-fault circuit-interrupter is to be
operated at a rate not to exceed ten times per minute provided that lamps, if used, are to be allowed to
be ″off″ at least 55 seconds before being energized. Tripping is allowed. See 32.8.
31 Low-Resistance Ground Fault Test
31.1 A ground-fault circuit-interrupter shall operate to interrupt the circuit when a low resistance ground
fault is present.
31.2 In order to determine compliance with the provisions of 31.1 the circuit is to be as described in 30.5.
The resistance R is to be adjusted for a value of current equal to six times the rating of the ground-fault
circuit-interrupter and connected as shown in Figure 31.1 so as to simulate a ground fault. The current is
to be initiated 25 times, at intervals of 10 seconds, or longer if necessary to reset the device. The 1-A fuse
(shown in Figure 31.1) connected to accessible conductive parts of the device shall not open. Automatic
interruption of the fault current is to occur each time in not more than T seconds as determined in
accordance with the equation
SEPTEMBER 18, 2000 GROUND-FAULT CIRCUIT-INTERRUPTERS - UL 943 43
and the average value of time for the 25 operations is not to exceed
The quantity V is the value of closed circuit voltage at the line terminals of the device.
This is generated text for figtxt.
Figure 31.1
Low-resistance ground-fault test circuit
SEPTEMBER 18, 2000 GROUND-FAULT CIRCUIT-INTERRUPTERS - UL 943 44
32 Endurance Test
32.1 A ground-fault circuit-interrupter shall have the necessary capacity for normal operation.
32.2 Except as permitted in 32.7, in order to determine compliance with 32.1, a ground-fault
circuit-interrupter is to be caused to switch an inductive load adjusted for a value of load current equal to
the ampere rating of the device and a power factor within the range of 0.75 – 0.80.
32.3 In performing the test described in 32.2, the device is to be switched ″on″ and, after one second,
switched ″off″ at a rate of approximately 6 cycles of operation per minute for 3000 cycles. An additional
3000 cycles are to be performed with automatic tripping by way of the supervisory circuit.
32.4 Reactive components of the load mentioned in 32.2 may be paralleled with each other if they are of
the air-core type. An air-core reactor is to be paralleled with resistance adjusted to dissipate approximately
one percent of the total power dissipated in the load without such resistance.
32.5 The value of paralleled resistance R in ohms mentioned in 32.4 may be obtained by calculation from
the relationship
in which E is the closed-circuit voltage at the load and I is the load current in amperes without resistance
R.
32.6 In performing the test described in 32.2, the capacity of the supply circuit is to be such as to allow
a closed-circuit voltage not less than 97.5 percent of the rated voltage of the ground-fault
circuit-interrupter. Except when a higher value is agreed to by those concerned, the open-circuit voltage
is to be in the range of 100 – 105 percent of the rated voltage of the ground-fault circuit-interrupter. A 1-A
fuse is to be connected between the grounded conductor of the supply circuit and accessible conductive
parts of the ground-fault circuit-interrupter. This fuse shall not operate to open the circuit.
32.7 A Class B ground-fault circuit-interrupter need be tested only with a tungsten-filament lamp or
equivalent load adjusted for rated current under steady-state conditions. The number of lamps is to be the
smallest possible using lamps of standard wattage ratings, provided that no lamp is rated more than 500
W without agreement of the submitter. Lamps are to be ″off″ at least 55 seconds.
32.8 In performing the test mentioned in 25.9, 30.7, and 32.7, the supply circuit shall be capable of
providing a peak current not less than 14.1 times the rms value of steady-state current in the load, within
1/240 second after the current is initiated. The voltage is to be as described in 32.6.
32.9 A sample that has been subjected to an endurance test need not withstand any other of the tests
described in these requirements.
SEPTEMBER 18, 2000 GROUND-FAULT CIRCUIT-INTERRUPTERS - UL 943 45
32.10 A ground-fault circuit-interrupter shall withstand being tripped by means of the supervisory circuit
and reset, at rated voltage without load, 25 times in as rapid succession as practicable.
33 Abnormal Operation Test
33.1 A ground-fault circuit-interrupter shall not become a shock or fire hazard when operating while in an
abnormal condition, such as with a short-circuited or open-circuited component.
33.2 A single layer of cheesecloth is to be loosely draped over the ground-fault circuit-interrupter. In
addition, a cord-connected device is to rest on white tissue paper supported by a softwood surface. A 1-A
fuse is to be connected between the grounded supply conductor and accessible conductive parts of the
device.
33.3 The cheesecloth mentioned in 33.2 is to be bleached cheesecloth running 14–15 square yards per
pound mass, (approximately 26–28 square meters per kilogram mass), and having what is known in the
trade as a ″count of 32 by 28″, that is, for any square inch, 32 threads in one direction and 28 threads in
the other direction (for any square centimeter, 13 threads in one direction and 11 in the other direction.)
33.4 A ground-fault circuit-interrupter operating under abnormal conditions will be considered to have
become a hazard if:
a) There is glowing or flaming of the cheesecloth or tissue paper mentioned in 33.2, or
b) There is emission of molten metal, or
c) The fuse mentioned in 33.2 operates to open the circuit, or
d) Except if the device is likely to be removed from service, there is dielectric failure (see 33.6
and 33.7), or
e) It is possible to touch a part with the articulated probe shown in Figure 33.1 while there is a
shock hazard at that part, or
f) There is any other evidence of hazard.
33.5 If normal operation of the supervisory circuit after abnormal operation provides an indication of
proper functioning of the ground-fault circuit-interrupter, the device shall be capable of complying with the
applicable provisions of 24.1.1 – 24.1.4.
33.6 Failure to comply with the provisions of 29.1 will be considered to be dielectric failure.
33.7 A device that is no longer able to complete the electric circuit to the load will be considered likely to
be removed from service.
SEPTEMBER 18, 2000 GROUND-FAULT CIRCUIT-INTERRUPTERS - UL 943 46
Figure 33.1
Articulated probe
SEPTEMBER 18, 2000 GROUND-FAULT CIRCUIT-INTERRUPTERS - UL 943 47
34 Extra-Low-Resistance Ground Faults Test
34.1 A ground-fault circuit-interrupter shall withstand extra-low-resistance ground faults.
34.2 In order to determine compliance with the provisions of 34.1, the supply circuit is to have an
open-circuit voltage in the range of 100 – 105 percent of the rating of the ground-fault circuit-interrupter.
The impedance of the supply is to be such as to provide a prospective current (the current that would
result from short-circuiting the supply terminals) shown in 34.3 or 34.4.
34.3 In testing a permanently connected ground-fault circuit-interrupter, the prospective current is to be
5000 A and the power factor is to be within the range of 0.45 – 0.50.
Exception: In testing a receptacle type ground-fault circuit-interrupter, the prospective current is to be
2000 A and the power factor is to be within the range of 0.90 – 1.0.
34.3 revised December 16, 1994
34.4 In testing a cord-connected ground-fault circuit-interrupter, the prospective current is to be 2000 A
and the power factor is to be within the range of 0.9 – 1.0.
34.5 Each line terminal of a ground-fault circuit-interrupter is to be connected to the supply mentioned in
34.2 using 4 ft (1.2 m) of insulated wire, both selected in accordance with Table 34.1. A fuse is to be
connected in series with the ungrounded line conductor. An identical conductor is to be connected
between a load terminal and a line terminal of the device so as to represent a ground fault. The device is
to be in any position considered to be normal in service. A 1-A fuse is to be connected between the supply
terminal representing the grounded circuit conductor and accessible conductive parts of the ground-fault
circuit-interrupter. Surgical cotton is to cover openings of the ground-fault circuit-interrupter where flame
may be emitted. See Figure 34.1.
Table 34.1
Fuse and wire
Ground–fault circuit interrupter rating, amperes
Cord–connected Permanently connected Series fuse amperes AWG conductor size
– 15 15 14
15 or 20 20 20 12
30 30 30 10
This is generated text for figtxt.
34.6 For a cord-connected circuit-interrupter, conductors are to be attached to the attachment plug blades
of the device and to a terminal of a receptacle of the device so as not to be dislodged during the test.
34.7 The prospective current is to be initiated once by means of a switch in the supply circuit, and once
by means of any control of the ground-fault circuit-interrupter, providing that a single sample need not
experience more than one current initiation. The 1-A fuse shall not operate to open the circuit, and there
shall be no flaming of the cotton, both mentioned in 34.5.
SEPTEMBER 18, 2000 GROUND-FAULT CIRCUIT-INTERRUPTERS - UL 943 48
35 Short Circuit Test
35.1 A ground-fault circuit-interrupter shall withstand short circuits.
35.2 In order to determine compliance with the provisions of 35.1, conditions are to be as described in
34.2 – 34.5, except that:
a) The ground fault described in 34.5 is not to be connected, and
b) A 20 inch (0.51 m) length of wire of the same construction as the line conductors is to be
connected between load terminals.
35.3 The test current is to be initiated by means of a switch in the supply circuit. The 1-A fuse shall not
operate to open the circuit and there shall be no flaming of the cotton, both mentioned in 34.5.
Figure 34.1
Extra-low-resistance ground-fault test circuit
SEPTEMBER 18, 2000 GROUND-FAULT CIRCUIT-INTERRUPTERS - UL 943 49
36 Chromic Acid Dropping Test
36.1 The solution to be used for the chromic acid dropping test is to be made from distilled water and is
to contain 200 grams per liter of reagent grade chromic acid (CrO 3 ) and 50 grams per liter of reagent
grade concentrated sulfuric acid (H 2 SO 4 ). (The latter is equivalent to 27 milliliters per liter of reagent grade
concentrated sulfuric acid, specific gravity of 1.84, containing 96 percent of H 2 SO 4 .)
36.2 The test solution is to be contained in a glass vessel such as a separatory funnel with the outlet
equipped with a stopcock and a capillary tube of approximate 0.025 inches (0.64 mm) inside bore and 5.5
inches (140 mm) long. The lower end of the capillary tube is tapered to form a tip, the drops from which
are about 0.05 mL each. To preserve an effectively constant level, a small glass tube is inserted in the top
of the funnel through a rubber stopper and its position is to be adjusted so that, when the stopcock is
open, the rate of dropping is 100 ±5 drops per minute. If desired, an additional stopcock may be used in
place of the glass tube to control the rate of dropping.
36.3 The sample and the test solution should be kept in the test room long enough to acquire the
temperature of the room, which should be noted and recorded. The test is to be conducted at a room
temperature of 70 – 90°F (21 – 32°C).
36.4 Each sample is to be thoroughly cleaned before testing. All grease, lacquer, paint, and other
nonmetallic coatings are to be removed completely by means of acceptable solvents. Samples are then
to be thoroughly rinsed in water and dried with clean cheesecloth. Care should be exercised to avoid
contact of the cleaned surface with the hands or any foreign material.
36.5 The sample to be tested is to be supported 0.7 – 1 inch (17 – 25 mm) below the orifice, so that the
drops of solution strike the point to be tested and run off quickly. The surface to be tested should be
inclined about 45 degrees from horizontal.
36.6 After cleaning, the sample to be tested is to be put in place under the orifice. The stopcock is to be
opened and the time in seconds is to be measured with a stop watch until the dropping solution dissolves
off the protective metal coating, exposing the base metal. The end point is the first appearance of the base
metal recognizable by the change in color at that point.
36.7 Each sample of a test lot is to be subjected to the test at three or more points, excluding cut,
stenciled, and threaded surfaces, on the inside surface and at an equal number of points on the outside
surface, at places where the metal coating may be expected to be the thinnest. On enclosures made from
precoated sheets, the external corners that are subjected to the greatest deformation are likely to have
thin coatings.
36.8 To calculate the thickness of the coating being tested, select from Table 36.1 the thickness factor
appropriate for the temperature at which the test was conducted and multiply by the time in seconds
required to expose base metal as noted in 36.6.
SEPTEMBER 18, 2000 GROUND-FAULT CIRCUIT-INTERRUPTERS - UL 943 50
Table 36.1
Coating thickness factors
Temperature, Thickness factors, 0.00001 inch (0.00025 mm) per second
°F (°C) Cadmium platings Zinc platings
70 (21.1) 1.331 0.980
71 (21.7) 1.340 0.990
72 (22.2) 1.352 1.000
73 (22.8) 1.362 1.010
74 (23.3) 1.372 1.015
75 (23.9) 1.383 1.025
76 (24.4) 1.395 1.033
77 (25.0) 1.405 1.042
78 (25.6) 1.416 1.050
79 (26.1) 1.427 1.060
80 (26.7) 1.438 1.070
81 (27.2) 1.450 1.080
82 (27.8) 1.460 1.085
83 (28.3) 1.470 1.095
84 (28.9) 1.480 1.100
85 (29.4) 1.490 1.110
86 (30.0) 1.501 1.120
87 (30.6) 1.513 1.130
88 (31.1) 1.524 1.141
89 (31.7) 1.534 1.150
90 (32.2) 1.546 1.160
37 Dust Test
37.1 To determine compliance with footnote b in Table 18.1, six samples, each mounted in a different
mounting orientation, are to be placed, deenergized, in an air-tight chamber having an internal volume of
at least 3 cubic feet (0.09 m 3 ).
37.2 Two oz (0.06 kg) of cement dust, maintained at a relative humidity of 20 – 50 percent and capable
of passing through a 200 mesh screen, is to be circulated for 15 minutes by means of compressed air or
a blower so as to completely envelop the sample in the chamber. The air flow is to be maintained at an
air velocity of approximately 50 fpm (0.25 m/s).
37.3 Following the exposure to dust, the sample exterior shall be carefully cleaned. The sample is then
to be opened and examined for the presence of dust. If there is no evidence of dust within the interior, the
sample can be considered ″closed-in″ for spacing purposes. See Table 18.1.
SEPTEMBER 18, 2000 GROUND-FAULT CIRCUIT-INTERRUPTERS - UL 943 51
37A Permanence of Marking
Added Section 37A effective July 4, 1995
37A.1 An adhesive backed label as mentioned in 39.1.2 and 39.2.2 shall comply with the Standard for
Marking and Labeling Systems, UL 969.
37A.2 Labels required by 39.2.2 that come in contact with uninsulated live parts shall be of a
nonconductive material that complies with the Dielectric Breakdown Test, Section 8, the Moisture
Absorption Test, Section 10 and the Test for Indirect Measurement of Conductor Corrosion, Section 15,
of the Standard for Electrical Insulating Tape, UL 510.
MARKINGS
38 Details
Section 38 Title revised January 4, 1995
38.1 General
Sub-heading 38.1 added and replaces 38.1 which has been relocated as added 39.1.1 January 4, 1995
38.1.1 A ground-fault circuit-interrupter shall be marked with the manufacturer’s name, trademark, or
other suitable means of identification and the electrical ratings in voltage, frequency, and load capacity in
amperes. The load-capacity marking of a cord-connected ground-fault circuit-interrupter shall include
watts.
38.13 relocated as added 38.1.1 January 4, 1995
38.1.2 A ground-fault circuit-interrupter shall be legibly and permanently marked with the date or other
dating period of manufacture not exceeding any three consecutive months.
Exception: The date of manufacture may be abbreviated, or may be in a nationally accepted
conventional code, or in a code affirmed by the manufacturer, provided that the code:
a) Does not repeat in less than 20 years, and
b) Does not require reference to the production records of the manufacturer to determine when
the product was manufactured.
38.18 relocated as added 38.1.2 January 4, 1995
38.1.3 An enclosure that has been found to be rainproof may be marked ″Rainproof″.
39.9 relocated as added 38.1.3 January 4, 1995
SEPTEMBER 18, 2000 GROUND-FAULT CIRCUIT-INTERRUPTERS - UL 943 52
38.2 Permanently connected ground-fault circuit-interrupters
Sub-heading 38.2 added and replaces 38.2 which has been relocated as added 39.2.9 January 4, 1995
38.2.1 Except if suitable wire connectors are packed with a ground-fault circuit-interrupter employing
terminal leads, the gauge of the terminal leads shall be marked on the device.
39.8 relocated as added 38.2.1 January 4, 1995
38.2.2 Unless a permanently connected ground-fault circuit-interrupter has been found suitable for use
where it may be exposed to rain, it shall be marked where visible during installation in letters 1/8 inch (3.2
mm) high with the words: ″Do not use where exposed to rain″, or the equivalent.
39.7 relocated as added 38.2.2 January 4, 1995
38.2.3 A ground-fault circuit-interrupter that has been found suitable for connection to a conduit which
extends directly to an underwater pool light forming shell may be so marked.
39.10 relocated as added 38.2.3 January 4, 1995
38.2.4 A permanently connected ground-fault circuit-interrupter shall have its terminals legibly and
permanently marked ″Line″ and ″Load″, and ″Hot″ and ″White″ as appropriate. If a permanently
connected ground-fault circuit-interrupter is provided with leads, the location where the leads exit the
ground-fault circuit-interrupter, shall be legibly and permanently marked ″Line″ and ″Load″, and ″Hot″ and
″White″ or ″Gray″ as appropriate.
Added 38.2.4 effective November 13, 1998
38.2.5 A permanently connected ground-fault circuit-interrupter shall be marked in letters at least 1/8 inch
(3.2 mm) high:
″For use on grounded circuits″.
For a Class A device:
″To minimize false tripping do not connect to swimming-pool equipment installed before
adoption of the 1965 National Electrical Code,″ and
For a Class B device:
″1. Use only with underwater swimming-pool lighting fixtures installed before adoption of the
1965 National Electrical Code. CAUTION – To prevent electrical shock, disconnect power
before servicing fixtures.
″2. To minimize false tripping: Do not connect to more than (____) feet (and/or ____ meters) of
load conductor for the total one-way run″. The blank shall be filled in with the appropriate
length, in accordance with Table 39.1. See also 25.3.
39.2.3 relocated as added 38.2.5 May 13, 1998
38.2.6 Marking of a permanently connected ground-fault circuit-interrupter shall include the Class.
39.2.12 relocated as added 38.2.6 May 13, 1998
SEPTEMBER 18, 2000 GROUND-FAULT CIRCUIT-INTERRUPTERS - UL 943 52A
38.3 Portable ground-fault circuit-interrupters
Sub-heading 38.3 added and replaces 38.3 which has been revised and relocated as added 39.1.2 January 4, 1995
38.3.1 A cord-connected ground-fault circuit-interrupter shall be marked in letters at least 1/8 inch (3.2
mm) high, with the word ″WARNING″ and the following or equivalent wording, ″To reduce the risk of
electric shock the supervisory circuit must be operated before an appliance is plugged into any receptacle
on the device. The marking shall describe the indication given by operation of the supervisory circuit and
inform the user that, in the event of an indication of improper functioning, the cause of the malfunction is
to be corrected before further use of the device.
38.11 relocated as added 38.3.1 January 4, 1995
38.3.2 A cord-connected device shall be marked with a statement to the effect that the device does not
guard against electric shock resulting from:
a) Some possible defects or faults in an extension cord or other wiring supplying the ground-
fault circuit-interrupter, or
b) Contact with both circuit conductors.
38.16 relocated as added 38.3.2 January 4, 1995
38.3.3 A cord connected ground-fault circuit-interrupter not provided with a permanently attached cord 6
ft (1.83 m) or longer in length, shall be marked with the following or equivalent wording ″This product
should be used only with a three-conductor, 120 volt, ____ ampere (15, 20, or 30 A) supply cord set
employing Type ST, SO, STO, SJT, SJO, or SJTO cord. In event of cord set damage, it should be
replaced only with an equivalent cord set″.
38.17 relocated as added 38.3.3 January 4, 1995
38.3.4 Unless a cord-connected ground-fault circuit-interrupter has been found suitable for use in wet
locations, it shall be marked ″Do not use where water is likely to enter case″ or the equivalent.
38.15 relocated as 38.3.4 January 4, 1995
38.4 Deleted effective July 4, 1995
38.5 Deleted effective July 4, 1995
38.6 Deleted effective July 4, 1995
38.7 Deleted effective July 4, 1995
38.8 Revised and relocated as added 39.2.10 January 4, 1995
38.9 Revised and relocated as added 39.2.11 January 4, 1995
38.10 Relocated as added 39.2.12 January 4, 1995
38.11 Relocated as added 38.3.1 January 4, 1995
APRIL 15, 2002 GROUND-FAULT CIRCUIT-INTERRUPTERS - UL 943 52B
38.12 Relocated as added 39.2.13 January 4, 1995
38.13 Relocated as added 38.1.1 January 4, 1995
38.14 Relocated as added 39.2.8 January 4, 1995
38.15 Relocated as added 38.3.4 January 4, 1995
38.16 Relocated as added 38.3.2 January 4, 1995
38.17 Revised and relocated as added 38.3.3 January 4, 1995
38.18 Relocated as added 38.1.2 January 4, 1995
39 Installation Instructions
39.1 General
Sub-heading 39.1 added and replaces 39.1 which has been relocated as added 39.2.1 January 4, 1995
39.1.1 There shall be plain, legible, and durable instructions for effective use of a ground-fault
circuit-interrupter. Whenever possible, such instructions are to appear on the device, and be so located
that they may be readily viewed without the use of tools, and while a permanently-connected device is
operating normally. A GFCI that can not accommodate legible instructions, due to the size of the
instructions, the size of the device, or both, may have the required instructions supplied on ″stuffer sheets″
provided with the GFCI. A receptacle-type GFCI shall be provided with an installation instruction sheet as
specified in 39.1.1.1.
Revised 39.1.1 effective November 13, 1998
39.1.1.1 Each receptacle-type GFCI shall be provided with the installation instructions shown in Figures
39.1 – 39.6. The installation instruction sheet, containing the detail of all six figures, shall not be smaller
than 8 – 1/2 inches (215.9 mm) high × 16 – 1/2 inches (419.1 mm) long, consisting of 12 panels (for
folding), each no smaller than 4 – 1/4 inches (108 mm) high × 2 – 3/4 inches (69.9 mm) long. The front
of the installation instructions shall contain the manufacturer’s name, cautionary note, and steps 1 – 6 as
shown in Figures 39.1 – 39.3. The back of the installation instruction sheet shall contain steps 7 and 8 as
shown in Figures 39.4 – 39.6. The only modifications that may be made to the content of the instructions
are those necessary for including the manufacturer’s name, model, and warranty information, and any
product configurations different from those represented in the figures. A GFCI that is provided with these
installation instructions need not additionally be provided with the instructions detailed in 39.2.4, 39.2.8, or
39.2.10.
Added 39.1.1.1 effective November 13, 1998
This is generated text for figtxt.
39.1.2 If the instructions in 39.1.1 are included on an adhesive-backed label, the label shall comply with
the requirements of 37A.1.
38.3 revised and relocated as added 39.1.2 effective July 4, 1995
SEPTEMBER 18, 2000 GROUND-FAULT CIRCUIT-INTERRUPTERS - UL 943 53
Figure 39.1
Installation instructions
Added Figure 39.1 effective November 13, 1998
SEPTEMBER 18, 2000 GROUND-FAULT CIRCUIT-INTERRUPTERS - UL 943 54
Figure 39.2
Installation instructions
Added Figure 39.2 effective November 13, 1998
SEPTEMBER 18, 2000 GROUND-FAULT CIRCUIT-INTERRUPTERS - UL 943 54A
Figure 39.3
Installation instructions
Added Figure 39.3 effective November 13, 1998
SEPTEMBER 18, 2000 GROUND-FAULT CIRCUIT-INTERRUPTERS - UL 943 54B
Figure 39.4
Installation instructions
Added Figure 39.4 effective November 13, 1998
SEPTEMBER 18, 2000 GROUND-FAULT CIRCUIT-INTERRUPTERS - UL 943 54C
Figure 39.5
Installation instructions
Added Figure 39.5 effective November 13, 1998
SEPTEMBER 18, 2000 GROUND-FAULT CIRCUIT-INTERRUPTERS - UL 943 54D
Pages 54 .E through 54 .F deleted.
Figure 39.6
Installation instructions
Added Figure 39.6 effective November 13, 1998
SEPTEMBER 18, 2000 GROUND-FAULT CIRCUIT-INTERRUPTERS - UL 943 55
39.2 Permanently connected ground-fault circuit-interrupters
Sub-heading 39.2 added and replaces 39.2 which has been relocated as added 39.2.3 January 4, 1995
39.2.1 Those installation instructions required to be on a permanently connected ground-fault
circuit-interrupter shall be either continuously exposed to view, or shall become exposed to view when the
field-wiring terminals are exposed to view.
39.1 relocated as added 39.2.1 January 4, 1995
39.2.2 A receptacle type GFCI shall be provided with an adhesive label that either covers the load
terminals or is wrapped around the load leads. The label shall be safety yellow in accordance with the
Standard for Product Safety Signs and Labels, ANSI Z535.4 or an equivalent yellow, with black lettering
and shall contain the following wording or equivalent: ″ATTENTION [in letters at least 3/32 inch (2.4 mm)
high]″ The load terminals under this label are for feeding additional receptacles. Miswiring can leave this
outlet without ground fault protection. Read instructions prior to wiring.″
Added 39.2.2 effective July 4, 1995
39.2.3 Relocated as added 38.2.5 May 13, 1998
39.2.4 A permanently connected ground-fault circuit-interrupter shall be provided with installation
instructions that include the following either in written text or pictorial form:
a) A description of how to differentiate ″Line″ conductors from ″Load″ conductors, and a
description of the proper method of connecting the conductors to the GFCI, and
b) A description of how to determine whether the GFCI has been wired properly and how to
determine whether it functions properly after it has been wired.
Added 39.2.4 effective July 4, 1995
39.2.5 Deleted May 13, 1998
39.2.6 A permanently connected ground-fault circuit-interrupter shall be clearly marked so as to minimize
the occurrence of miswiring of the conductors to the means of termination provided. See 15.7.
39.5 revised and relocated as added 39.2.6 January 4, 1995
39.2.7 In determining compliance with the provisions of 39.2.6, consideration is to be given to:
a) Wire gauge,
b) Whether conductors are copper or aluminum,
c) Whether terminals are for grounded, grounding, line, or load connection, and
d) Whether conductors are solid or stranded.
39.6 revised and relocated as added 39.2.7 January 4, 1995
39.2.8 A statement to the effect that the device does not guard against electric shock resulting from
contact with both circuit conductors shall appear on a permanently connected ground-fault
circuit-interrupter or in literature packed with the device.
38.14 relocated as added 39.2.8 January 4, 1995
SEPTEMBER 18, 2000 GROUND-FAULT CIRCUIT-INTERRUPTERS - UL 943 56
39.2.9 There is to be suitable reference on a ground-fault circuit-interrupter to the location of any of the
instructions mentioned in 39.1.1, that are not on the device.
38.2 revised and relocated as added 39.2.9 January 4, 1995
39.2.10 For a permanently connected ground-fault circuit-interrupter, there shall be instructions to operate
the supervisory circuit upon installation and at least as frequently as monthly. Part of these instructions
may be omitted from the device when complete instructions are provided on literature packaged with the
device.
38.8 relocated as 39.2.10 January 4, 1995
39.2.11 The instructions mentioned in 39.2.10 shall include on the device a description of the indication
given by instructions for the normal operation of the supervisory circuit.
38.9 revised and relocated as added 39.2.11 January 4, 1995
39.2.12 Relocated as added 38.2.6 May 13, 1998
39.2.13 Deleted May 13, 1998
39.3 Deleted January 4, 1995
Table 39.1
Marked length
Volt-ampere rating of interrupter
Marked length of load conductor run in feet, (meters)
minimum
Not over 600 100
Over 600 but not over 1200 150
Over 1200 but not over 1800 175
Over 1800 but not over 2400 200
Over 2400 but not over 3600 250
39.4 Revised and relocated as added 39.2.5 January 4, 1995
39.5 Revised and relocated as added 39.2.6 January 4, 1995
39.6 Revised and relocated as added 39.2.7 January 4, 1995
39.7 Relocated as added 39.2.2 January 4, 1995
39.8 Relocated as added 38.2.1 January 4, 1995
39.9 Relocated as added 38.1.3 January 4, 1995
39.10 Relocated as added 38.2.3 January 4, 1995
SEPTEMBER 18, 2000 GROUND-FAULT CIRCUIT-INTERRUPTERS - UL 943 57
SEPTEMBER 18, 2000 GROUND-FAULT CIRCUIT-INTERRUPTERS - UL 943 58
No Text on This Page
SUPPLEMENT SA - OPTIONAL 10 KA SHORT CIRCUIT CURRENT TEST FOR OUTLET-BOX TYPE
GROUND-FAULT CIRCUIT-INTERRUPTERS.
INTRODUCTION
SA1 Scope
Section SA1 added March 24, 1997
SA1.1 These requirements in this supplement cover an optional test procedure for a ground-fault
circuit-interrupter.
SA1.2 These requirements are intended to verify the optional 10kA short circuit current capabilities for a
ground-fault circuit-interrupter employed in applications such as power outlets, where higher currents are
available.
SA1.3 The ground-fault circuit-interrupter mentioned in SA1.2 shall comply with the applicable
requirements of this standard, UL 943, except as modified by the requirements contained in this
supplement.
SA1.4 The requirements of this supplement do not apply to a portable ground-fault circuit-interrupter.
PERFORMANCE
SA2 General
Section SA2 added March 24, 1997
SA2.1 Representative outlet-box type ground-fault circuit-interrupters shall be subjected to the Extra-Low-
Resistance Ground Fault Test in Section 34 and the Short Circuit Test in Section 35 except the
prospective current is to be 10,000 rms Symmetrical Amperes and the power factor in the range of 0.45
to 0.50.
SA2.2 In the tests mentioned in SA2.1 each representative device tested shall be operational after each
test. Operation shall be verified by the supervisory circuit remaining operable upon completion of each
test. The representative devices tested shall also comply with Dielectric Voltage-Withstand Test, Section
29. See also 21.2 for representative device selection.
SEPTEMBER 18, 2000 GROUND-FAULT CIRCUIT-INTERRUPTERS - UL 943 SA1
MARKINGS
SA3 General
Section SA3 added March 24, 1997
SA3.1 A ground-fault circuit-interrupter that complies with SA2.1 and SA2.2 shall not be marked to
indicate the ability to withstand a 10kA short circuit current as a result of these tests.
SEPTEMBER 18, 2000 GROUND-FAULT CIRCUIT-INTERRUPTERS - UL 943 SA2
APPENDIX A
Standards for Components
Standards under which components of the products covered by this standard are evaluated include the
following:
Title of Standard − UL Standard Designation
Attachment Plugs and Receptacles – UL 498
Boxes, Junction, for Swimming Pool Lighting Fixtures – UL 1241
Cord Sets and Power-Supply Cords – UL 817
Double Insulation Systems for Use in Electrical Equipment – UL 1097
Flexible Cord and Fixture Wire – UL 62
Fuseholders – UL 512
Industrial Control Equipment – UL 508
Optical Isolators – UL 1577
Plastic Materials for Parts in Devices and Appliances, Tests for Flammability of – UL 94
Polymeric Materials – Long Term Property Evaluations – UL 746B
Polymeric Materials – Short Term Property Evaluations – UL 746A
Polymeric Materials – Use in Electrical Equipment Evaluations – UL 746C
Printed-Wiring Boards, Electrical – UL 796
Semiconductor Devices, Electrically Isolated – UL 1557
Sharpness of Edges on Equipment, Determination of – UL 1439
Switches, Special-Use – UL 1054
Systems of Insulating Materials – General – UL 1446
Tape, Insulating – UL 510
Terminal Blocks, Electrical – UL 1059
Terminals, Electrical Quick-Connect – UL 310
Tubing, Extruded Insulating – UL 224
Wire Connectors and Soldering Lugs for Use With Copper Conductors – UL 486A
Wire Connectors for Use With Aluminum Conductors – UL 486B
Wire Connectors, Splicing – UL 486C
Wires and Cables, Rubber-Insulated – UL 44
Wires and Cables, Thermoplastic-Insulated – UL 83
Wiring Terminals, Equipment, for Use With Aluminum and/or Copper Conductors – UL 486E
MAY 13, 1998 GROUND-FAULT CIRCUIT-INTERRUPTERS - UL 943 A1
MAY 13, 1998 GROUND-FAULT CIRCUIT-INTERRUPTERS - UL 943 A2
No Text on This Page